ProSoft Technology MVI69-DNP User Manual
Page 113
Reference MVI69-DNP
♦ CompactLogix or MicroLogix Platform
DNP 3.0 Master/Slave Communication Module
ProSoft Technology, Inc.
Page 113 of 129
November 3, 2008
OBJECT
REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
4
16-Bit Delta Counter
129, 130 00, 01
24
Master will process this
variation
5
32-Bit Binary
Counter Without Flag
1, 7, 8,
9, 10
06
129, 130 00, 01
32
Master will generate and
process this variation
6
16-Bit Binary
Counter Without Flag
1, 7, 8,
9, 10
06
129, 130 00, 01
16
Master will generate and
process this variation
7
32-Bit Delta Counter
Without Flag
129, 130 00, 01
32
Master will process this
variation
8
16-Bit Delta Counter
Without Flag
129, 130 00, 01
16
Master will process this
variation
21
0
Frozen Counter: All
Variations
1
06
32
Master will generate this
variation
1
32-Bit Frozen
Counter
129, 130 00, 01
40
Master will process this
variation
2
16-Bit Frozen
Counter
129, 130 00, 01
24
Master will process this
variation
3
32-Bit Frozen Delta
Counter
40
4
16-Bit Frozen Delta
Counter
24
5
32-Bit Frozen
Counter With Time
Of Freeze
88
6
16-Bit Frozen
Counter With Time
Of Freeze
72
7
32-Bit Frozen Delta
Counter With Time
Of Freeze
88
8
16-Bit Frozen Delta
Counter With Time
Of Freeze
72
9
32-Bit Frozen
Counter Without Flag
1
06
129, 130 00, 01
32
Master will generate and
process this variation
10
16-Bit Frozen
Counter Without Flag
1
06
129, 130 00, 01
16
Master will generate and
process this variation
11
32-Bit Frozen Delta
Counter Without Flag
32
12
16-Bit Frozen Delta
Counter Without Flag
16
22 0 Counter
Change
Event: All Variations
1
06, 07, 08
Master will not generate a
request for this variation
1
32-Bit Counter
Change Event
Without Time
129, 130 17, 28
40
Master will process this