MVI69-DNP ♦ CompactLogix or MicroLogix Platform
Reference
DNP 3.0 Master/Slave Communication Module
Page 86 of 129
ProSoft Technology, Inc.
November 3, 2008
Word Offset in Block Data Field(s)
Description
5 Minute
This field contains the minute value for the new
time. Valid entry for this field is in the range of 0
to 59.
6 Seconds
This field contains the second value for the new
time. Valid entry for this field is in the range of 0
to 59.
7 Milliseconds
This field contains the millisecond value for the
new time. Valid entry for this field is in the range
of 0 to 999.
8 to 61
Not Used
Not Used
Warm Boot
This block is sent from the CompactLogix or MicroLogix processor to the module
(output image) when the module is required to perform a warm-boot (software
reset) operation. This block is commonly sent to the module any time
configuration data modifications are made in the controller tags data area. This
will force the module to read the new configuration information and to restart. The
structure of the control block is shown below:
Offset Description
Length
0 9998
1
1 to 63
Spare
63
Cold Boot
This block is sent from the CompactLogix processor to the module (output
image) when the module is required to perform the cold boot (hardware reset)
operation. This block is sent to the module when a hardware problem is detected
by the ladder logic that requires a hardware reset. The structure of the control
block is shown in the following table.
Offset Description
Length
0 9999
1
1 to 63
Spare
63