ProSoft Technology MVI69-DNP User Manual
Page 101

Reference MVI69-DNP
♦ CompactLogix or MicroLogix Platform
DNP 3.0 Master/Slave Communication Module
ProSoft Technology, Inc.
Page 101 of 129
November 3, 2008
Error
Code
Name Description
225
Invalid DNP unsolicited
response mode
The unsolicited response mode code is not valid in the
configuration.
226
Invalid DNP unsolicited
response minimum
quantity for Class 1
The unsolicited response minimum quantity for Class 1 is not
valid in the configuration. Value must be an integer in the
range of 1 to 255.
227
Invalid DNP unsolicited
response minimum
quantity for Class 2
The unsolicited response minimum quantity for Class 2 is not
valid in the configuration. Value must be an integer in the
range of 1 to 255.
228
Invalid DNP unsolicited
response minimum
quantity for Class 3
The unsolicited response minimum quantity for Class 3 is not
valid in the configuration. Value must be an integer in the
range of 1 to 255.
230
Invalid DNP unsolicited
response destination
address
The unsolicited response destination address is not valid in
the configuration. Value must be in the range of 1 to 65534.
Command Error Codes
General Command Errors
Error
Code
Name Description
1 Device
not
defined
The IED slave address referenced in the command is not
defined in the module. Check to make sure there is an entry
in the slave table for each slave device referenced in the
command list.
2 Invalid
command
This command is not valid. Check to make sure the slave
address parameter is greater than or equal to zero and that
the point count is not set to zero.
3
Object not supported
The data object in the command is not supported by the
module. Refer to the DNP subset for the Master Port.
4
Command function not
supported
The function specified in the command is not supported for
the object type selected. Refer to the DNP subset for the
Master Port.
10
Invalid binary input poll
command
This binary input object command is not valid.
11
Invalid binary input
event poll command
This binary input event object poll command is not valid.
20
Invalid binary output
command function
This binary output command function is not valid.
30
Invalid counter poll
command function
The counter object poll command contains an invalid function
code.
31
Invalid counter poll
command
This counter object poll command is not valid.
40
Invalid frozen counter
poll command
This frozen counter object poll command is not valid.
50
Invalid analog input poll
command
This analog input poll command is not valid.
51
Invalid analog input
event poll command
This analog input event poll command is not valid.