beautypg.com

Dnp subset definition - master, 8 dnp subset definition - master – ProSoft Technology MVI69-DNP User Manual

Page 112

background image

MVI69-DNP ♦ CompactLogix or MicroLogix Platform

Reference

DNP 3.0 Master/Slave Communication Module

Page 112 of 129

ProSoft Technology, Inc.

November 3, 2008

OBJECT

REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

23

Slave supports the Delay
Measurement & Time
Synchronization Function
and will return Obj 52, Var
2, Qual 7, Cnt 1

5.8

DNP Subset Definition - Master

OBJECT

REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

1

0

Binary Input: All
Variations

1

06

1

Master will generate this
variation

1

Binary Input

1

06

129, 130 00, 01

1

Master will generate and
process this variation

2

Binary Input with
Status

1

06

129, 130 00, 01

8

Master will generate and
process this variation

2

0

Binary Input Change:
All Variations

1

06, 07, 08

56

Master will generate this
variation

1

Binary Input Change
Without Time

1

06, 07, 08 129, 130 17, 28

8

Master will generate and
process this variation

2

Binary Input Change
With Time

1

06, 07, 08 129, 130 17, 28

56

Master will generate and
process this variation

3

Binary Input Change
With Relative Time

1

06, 07, 08 129, 130 17, 28

24

Master will generate and
process this variation

10

0

Binary Output: All
Variations

1

06

8

1

Binary Output

1

2

Binary Output Status

129, 130 00, 01

8

Master does not use this
object type and will not
generate a message or
process this type

12

0

Control Block: All
Variations

88

1

Control Relay Output
Block

3, 4, 5, 6 17, 28

129

Echo of
request

88

Master will generate this
variation and parse the
response

2

Pattern Control Block

88

3

Pattern Mask

16

20

0

Binary Counter: All
Variations

1, 7, 8,
9, 10

06

32

Master will generate this
variation

1

32-Bit Binary
Counter

129, 130 00, 01

40

Master will process this
variation

2

16-Bit Binary
Counter

129, 130 00, 01

24

Master will process this
variation

3

32-Bit Delta Counter

129, 130 00, 01

40

Master will process this
variation