ProSoft Technology MVI69-DNP User Manual
Page 83
![background image](https://www.manualsdir.com/files/866098/content/doc083.png)
Reference MVI69-DNP
♦ CompactLogix or MicroLogix Platform
DNP 3.0 Master/Slave Communication Module
ProSoft Technology, Inc.
Page 83 of 129
November 3, 2008
Word Offset in Block Data Field(s)
Description
13 to 17
Five words of data for Event #3.
18 to 22
Five words of data for Event #4.
23 to 27
Five words of data for Event #5.
28 to 32
Five words of data for Event #6.
33 to 37
Five words of data for Event #7.
38 to 42
Five words of data for Event #8.
43 to 47
Five words of data for Event #9.
48 to 52
Five words of data for Event #10.
53 to 57
Five words of data for Event #11.
58 to 61
Spare
Not Used
To ensure the receipt of this block of information, the module returns a block
9958 with the sequence counter set to the value of the last successful block 9958
received.
Block Format for Read
Word Offset in Block Data Field(s)
Description
0
Block ID
Identification code for block set to 9958.
1 Block
ID
Block identification code for request from PLC by
the module.
2 Event
Count
This field contains the number of events
processed by the module.
3 Sequence
Counter
This field contains the sequence counter of the
last successful block 9958 received.
4 to 61
Spare
Not used
Block 9959 - Processor Analog Input Event
If the processor sends a block 9959, the module will place the analog input event
data in the block into the event buffer and alter the data values for the points in
the DNP analog input database. The format for the event message is shown in
the following table.
Block Format for Write
Word Offset in Block Data Field(s)
Description
0 Block
ID
This field contains the value of 9959 identifying
the event block to the module.
1 Event
Count
This field contains the number of events
contained in the block. Valid values for this field
are 1 to 9.
2 Sequence
Counter
This field holds the sequence counter for each
9959 block transfer. This synchronizes and
confirms receipt of the block by the module.
3
DNP Analog Input Data
point
This is the data point in the DNP analog input
database represented by the event.
4
Analog Input Value
This is the new analog input value represented
in the event.