5.6
DNP V3.00 Device Profile Document
Vendor Name:
ProSoft Technology, Inc.
Device Name:
MVI69-DNP (Revision 1.00)
Highest DNP Level Supported:
Device Function:
For Request: L2
For Responses: L2
Slave & Master
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP level stated above (see attached
table for complete list):
Definition of selected IIN bits: Configuration Error - User specified point or event count is too high for application (can only
correct by changing configuration in PLC).
Support for a redundant slave port on the module which may be attached to a dial-up modem is provided. Auto switching
is provided by the module to switch between the primary and secondary ports.
The following features are configurable on the module: Collision avoidance, time sync before events are generated and
default analog input events, Obj32V4 or O32V2, select option.
Events generated by IED units attached to a master port may pass their events directly to the slave port. These events
may not occur in the correct time sequence. They are placed in the event buffer as the module receives them. This
provides the greatest time resolution for remote events.
Module will not generate events until Restart IIN bit is cleared by DNP master except for events passed through module
from attached IED units.
Maximum Data Link Frame Size (octets):
Maximum Application Fragment Size (octets):
Transmitted: 292
Received: 292
Transmitted: 2048
Received: 2048
Maximum Data Link Re-tries:
Maximum Application Layer Retries:
Configurable from 0 - 255
None
Requires Data Link Layer Confirmation:
Configurable at module start-up (never, sometimes, & always)
Requires Application Layer Confirmation:
When reporting Event Data as a slave unit
Time-outs while waiting for:
Data Link Confirm
: Configurable at module start-up (1 to 65535 milliseconds)
Complete Application Fragment
: Configurable at module start-up
Application Confirm
: Configurable at module start-up (1 to 65535 milliseconds)
Complete Application Response
: None
Sends/Executes Control Operations:
WRITE Binary Outputs
: Never
SELECT/OPERATE :
Always
DIRECT OPERATE
: Always
DIRECT OPERATE-NO ACK
: Always
Count > 1
: Always (1 to 65535)
Pulse On
: Always
Pulse Off
: Always
Latch On
: Always
Latch Off
: Always