ProSoft Technology MVI69-DNP User Manual
Page 33

Configuring the MVI69-DNP Module
MVI69-DNP ♦ CompactLogix or MicroLogix Platform
DNP 3.0 Master/Slave Communication Module
ProSoft Technology, Inc.
Page 33 of 129
November 3, 2008
2.4.1 Slave
Address
This parameter specifies the IED unit address on the DNP network to consider
with the command. The parameter has a range of 0 to 65535. The value of
65535 is reserved for broadcast messages. Verify that the slave configuration
information is set up in the module for each slave defined in the command list.
2.4.2 Object
This parameter specifies the DNP object type in the command. Valid objects for
the module are 1, 2, 12, 20, 21, 30, 32, 41, 50, 60 and 80. A value of 0 is
permitted in this field for a set of special commands.
2.4.3 Variation
This parameter is specific to the object type selected.
2.4.4 Function
This parameter specifies the DNP function for the command list object. The
object type determines the value of the functions permitted. For example, the
only function permitted for binary input data points is the read function (Function
Code 1). For counter and output objects, more functions are available.
2.4.5 Address In Slave
This value must be greater-than or equal to zero. If it is set to a value less-than
zero, the command will be ignored. This parameter specifies the starting point
address to consider in the IED unit.
2.4.6 Point
Count
This parameter defines the number of points in the IED unit. Refer to the
discussion above for the interpretation of this parameter's values for the different
object types.
2.4.7 DNP
DB
Address
This parameter defines the starting location in the DNP database to be used with
the command. If the parameter has a value of -1, the DNP database is not used
with the point.
2.4.8 IED
DB
Address
This parameter defines the starting location in the IED database to be used with
the command. If the parameter has a value of -1, the IED database is not used
with the point.