OBJECT

REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

3

32-Bit Frozen Analog
Event With Time

88

4

16-Bit Frozen Analog
Event With Time

72

40 0 Analog

Output

Status: All Variations

1

06

24

1

32-Bit Analog Output
Status

40

2

16-Bit Analog Output
Status

129, 130 00, 01

24

Master does not use this
object type and will not
generate a message or
process this type

41

0

Analog Output Block:
All Variations

24

1

32-Bit Analog Output
Block

40

2

16-Bit Analog Output
Block

3, 4, 5, 6 17, 28

129

Echo of
Request

24

Master will generate this
variation and parse the
response

50

0

Time and Date: All
Variations

48

1

Time and Date

2

07, With
Quant=1

48

Master will generate this
variation

2

Time and Date With
Interval

80

51

0

Time and Date CTO:
All Variations

1

Time and Date CTO

129, 130 07, With

Quant=1

48

Master will process this
variation

2

Unsynchronized
Time and Date CTO

129, 130 07, With

Quant=1

48

Master will process this
variation

52

0

Time Delay: All
Variations

1

Time Delay Coarse

129

07, With
Quant=1

16

Master will not process
this variation

2

Time Delay Fine

129

07, With
Quant=1

16

Master will not process
this variation

60

0

Not Defined

Not Defined in DNP

1

Class 0 Data

1

06

Master will generate this
variation

2

Class 1 Data

1

06, 07, 08

Master will generate this
variation

3

Class 2 Data

1

06, 07, 08

Master will generate this
variation

4

Class 3 Data

1

06, 07, 08

Master will generate this
variation

70

0