ProSoft Technology MVI69-DNP User Manual
Page 116
MVI69-DNP ♦ CompactLogix or MicroLogix Platform
Reference
DNP 3.0 Master/Slave Communication Module
Page 116 of 129
ProSoft Technology, Inc.
November 3, 2008
OBJECT
REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
3
32-Bit Frozen Analog
Event With Time
88
4
16-Bit Frozen Analog
Event With Time
72
40 0 Analog
Output
Status: All Variations
1
06
24
1
32-Bit Analog Output
Status
40
2
16-Bit Analog Output
Status
129, 130 00, 01
24
Master does not use this
object type and will not
generate a message or
process this type
41
0
Analog Output Block:
All Variations
24
1
32-Bit Analog Output
Block
40
2
16-Bit Analog Output
Block
3, 4, 5, 6 17, 28
129
Echo of
Request
24
Master will generate this
variation and parse the
response
50
0
Time and Date: All
Variations
48
1
Time and Date
2
07, With
Quant=1
48
Master will generate this
variation
2
Time and Date With
Interval
80
51
0
Time and Date CTO:
All Variations
1
Time and Date CTO
129, 130 07, With
Quant=1
48
Master will process this
variation
2
Unsynchronized
Time and Date CTO
129, 130 07, With
Quant=1
48
Master will process this
variation
52
0
Time Delay: All
Variations
1
Time Delay Coarse
129
07, With
Quant=1
16
Master will not process
this variation
2
Time Delay Fine
129
07, With
Quant=1
16
Master will not process
this variation
60
0
Not Defined
Not Defined in DNP
1
Class 0 Data
1
06
Master will generate this
variation
2
Class 1 Data
1
06, 07, 08
Master will generate this
variation
3
Class 2 Data
1
06, 07, 08
Master will generate this
variation
4
Class 3 Data
1
06, 07, 08
Master will generate this
variation
70
0
Not Defined