ProSoft Technology MVI69-DNP User Manual
Page 25
Configuring the MVI69-DNP Module
MVI69-DNP ♦ CompactLogix or MicroLogix Platform
DNP 3.0 Master/Slave Communication Module
ProSoft Technology, Inc.
Page 25 of 129
November 3, 2008
[Section]/Item Value
Range
Description
Unsol Resp Delay:
0 to 65535
milliseconds
Maximum number of 1 millisecond intervals to wait
after an event occurs before sending an unsolicited
response message. If set to 0, only use minimum
number of events.
Uresp Master Address:
0 to 65534
DNP destination address where unsolicited response
messages are sent.
Uresp Retry Count:
0 to 255 retries Determines the number of unsolicited message retries
sent on primary DNP port before changing to
secondary port. If the value is 0, port switching will be
disabled.
AI Events with time:
Yes or No
This parameter sets if the analog input events
generated by the module will include the date and time
of the event. If the parameter is set to No, the default is
set to no time data. If the parameter is set to Yes, the
default object will include the time of the event.
Time Sync Before Events:
Yes or No
This parameter determines if events are to be
generated by the module before the time
synchronization from the master unit. If the parameter
is set to No, no events will be generated until the
module's time has been synchronized. If the parameter
is set to Yes, events will always be generated.
Initialize DNP Database:
Y or N
This parameter determines if the module will request
data from the processor to initialize the DNP database
output data areas. If this option is utilized, ladder logic
is required to send the requested block from the
processor to the module.
Use Trip/Close Single Point
Y or N
Used for backwards compatibility with older MVI69-
DNP modules, will cause Trip/Close operations to use
a single point operation.
[Section]/Item Value
Range
Description
[DNP Slave Database]
DNP Slave Database definition
Binary Inputs:
0 to 7680
points
Number of digital input points to configure in the DNP
slave device. Each point will be stored as a single bit in
the module memory.
PLC Binary Inputs:
0 to 7680
points
Number of digital input points configured above that
are to be obtained from the CompactLogix processor.
All other binary input points must come from the
attached IED units.
Analog Inputs:
0 to 480 points Number of analog input points to configure in the DNP
slave device. Each point will occupy a one word area
in the module memory.
PLC Analog Inputs:
0 to 480 points Number of analog input points configured above that
are to be obtained from the CompactLogix processor.
All other analog input points must come from the
attached IED units.
Float Inputs:
0 to 240 points Number of floating-point input points to configure in the
DNP slave device. Each point will occupy a two-word
area in the module memory.
PLC Float Inputs:
0 to 240 points Number of floating-point input points configured above
that are to be obtained from the PLC.
Counters:
0 to 240 points Number of counter points to configure in the DNP
slave device. Each point will occupy a two word area in
the module memory. This number corresponds to the
number of frozen counters. The application maps the
counters to the frozen counters directly.