ProSoft Technology MVI69-DNP User Manual
Page 26
![background image](https://www.manualsdir.com/files/866098/content/doc026.png)
MVI69-DNP ♦ CompactLogix or MicroLogix Platform
Configuring the MVI69-DNP Module
DNP 3.0 Master/Slave Communication Module
Page 26 of 129
ProSoft Technology, Inc.
November 3, 2008
[Section]/Item Value
Range
Description
PLC Counters:
0 to 240 points Number of counter points configured above that are to
be obtained from the CompactLogix processor. All
other counter points must come from the attached IED
units.
Binary Outputs:
0 to 7680
points
Number of digital output points to configure in the DNP
slave device. Each point will be stored as a single bit in
the module memory.
PLC Binary Outputs:
0 to 7680
points
Number of digital output points configured above that
are to be sent to the CompactLogix processor. All
other binary output points will be sent to the attached
IED units.
Analog Outputs:
0 to 480 points Number of analog output points to configure in the
DNP slave device. Each point will occupy a one word
area in the module memory.
PLC Analog Outputs:
0 to 480 points Number of analog output points configured above that
are to be sent to the CompactLogix processor. All
other analog output points will be sent to the attached
IED units.
Float Outputs:
0 to 240 points Number of floating-point output points to configure in
the DNP slave device. Each point will occupy a two-
word area in the module memory.
PLC Float Outputs:
0 to 240 points Number of floating-point output points configured
above that are to be sent to the CompactLogix.
[Section]/Item
Description
[DNP Slave Binary Inputs]
DNP database binary input override values
# This area is to override the class assignment for binary input database points. Enter list of points between the
# START and END labels.
#
# Point# Class
START
END
[Section]/Item
Description
[DNP Slave Analog Inputs]
DNP database analog input override values
START
# This area is to override the class and deadband assignment for analog input database points.
# Enter list of points between the START and END labels.
#
# Point# Class Deadband
START
END
[Section]/Item
Description
[DNP Slave Float Inputs]
DNP database floating-point input override values
# This area is to override the class and deadband assignment for float input database points.
# Enter list of points between the START and END labels.
#
# Point# Class Deadband