ProSoft Technology MVI69-DNP User Manual
Page 100
![background image](https://www.manualsdir.com/files/866098/content/doc100.png)
MVI69-DNP ♦ CompactLogix or MicroLogix Platform
Reference
DNP 3.0 Master/Slave Communication Module
Page 100 of 129
ProSoft Technology, Inc.
November 3, 2008
System Configuration Errors
Error
Code
Name Description
100
Too many binary input
points
Too many binary input points are configured for the module.
Maximum value is 7680
101
Too many binary output
points
Too many binary output points are configured for the module.
Maximum value is 7680
102
Too many counter
points
Too many counter points are configured for the module.
Maximum value is 240
103
Too many analog input
points
Too many analog input points are configured for the module.
Maximum value is 480
104
Too many analog input
points
Too many analog output points are configured for the
module. Maximum value is 480
105
Too many binary input
events
Too many binary input events are configured for the module.
Maximum value is 400.
106
Too many analog input
events
Too many analog input events are configured for the module.
Maximum value is 400.
107
Invalid analog input
deadband
Deadband value for analog input events is out of range.
Value must be in the range of 0 to 32767.
108
Not enough memory
There is not enough memory in the module to configure the
module as specified.
109
Invalid block transfer
delay for blocks
error/status blocks
Block transfer delay value specified is too low.
110
File count invalid
The file count must be in the range of 0 to 6.
111
Invalid file record size
The file record size must be in the range of 1 to 120.
112
Invalid block
identification code for
file
The file block transfer code must be in the range of 100 to
120.
DNP Port Configuration Errors
Error
Code
Name Description
212
Invalid DNP address
The DNP address specified in the configuration is not valid (0
to 65534).
213
Invalid DNP port baud
rate
The baud rate code specified in the configuration is not valid.
219
Invalid DNP data link
layer confirm mode
The data link confirmation mode code is not valid in the
configuration.
220
Invalid DNP data link
confirm time-out
The data link time-out period specified in the configuration is
0. It must be an integer in the range of 1 to 65535.
222
Invalid DNP
select/operate arm time
duration
The select/operate arm timer is set to 0. It must be an integer
in the range of 1 to 65535.
223
Invalid DNP application
layer confirm time-out
The application layer confirm time-out value is set to 0. It
must be an integer in the range of 1 to 65535.
224
Invalid DNP write time
interval
The write time interval is not in the data range in the
configuration. The value must be in the range of 0 to 1440.