beautypg.com

3 series connection, Ar. 2.4.3 – KEPCO RA 19-4C Operator Manual User Manual

Page 37

background image

RA 19-4C 121013

2-19

2.4.3

SERIES CONNECTION

HSF power supplies may be connected in series to obtain higher output voltages. The RA 19-
4C rack adapter is designed to safely handle a maximum output voltage of 500 Volts; contact
Kepco Applications Engineering for additional information. The power supply with the lowest
rated value of maximum current establishes the maximum load current allowed. Series configu-
rations can only be accomplished by external wiring of the I/O mating connector.

For series operation, connect (+) and (–) terminals at the DC OUTPUT terminal block of power
supplies to be connected in series. Bus bars are available as accessories to make these con-
nections when connecting adjacent slots in series (refer to Table 1-2).

The DC OUTPUT + terminal of one supply must be connected to DC OUTPUT – terminal of the
next supply. Each Power Supply in series must be protected by a diode connected in parallel
with the output as shown in Figure 2-11. The diode protects against reverse voltages. For con-
venience, bus bars are available as accessories to connect adjacent slots in series (refer to
Table 1-2). The bus bars can also serve as heat sinks for the diodes (see Figure 2-21). Protec-
tion diodes must conform to the following specifications:

• V

REV

> 2 x V

NOM

x N where V

NOM

is the output voltage of the HSF power supply and N

is the number of power supplies connected in series.

• I

FWD

> 1.5 x I

NOM

where I

NOM

is the output current of the HSF power supply.

Rack adapter DIP switches positions 1 through 5 must be set to OFF (open) on all DIP switches
between series-connected modules (refer to Figure 1-5).

Table 2-4 lists the settings for the HSF DIP switches required to configure HSF power supplies
to use either local or remote control.

TABLE 2-4. HSF DIP SWITCH CONFIGURATION FOR VOLTAGE CONTROL OF

MULTIPLE UNITS IN SERIES

HSF DIP
SWITCH

POSITION
(See Note)

HSF 300W, 600W

HSF 1200W, 1500W

Vadj Control

External R or V

Vadj Control

External R or V

SW2

SW1

SW2

SW1

SW2

SW1

SW2

SW1

Position 1 (REF)

OFF

ON

ON

OFF

OFF

ON

ON

OFF

Position 2 (RV)

OFF

ON

ON

OFF

OFF

ON

ON

OFF

Position 7 (COM)

OFF

See

Note (2)

ON

See

Note (2)

OFF

ON

ON

OFF

NOTES:
(1) HSF DIP Switches are located at the rear of each HSF module; refer to appropriate HSF manual for location.
(2) For HSF 600W, set SW1 position 7 to OFF

For HSF 300W, SW1 position 7 allows the DC ON indicator to powered by an internal auxiliary supply (see HSF

300W Operator Manual for details).