beautypg.com

2 group control, Group control -11 – KEPCO RA 19-4C Operator Manual User Manual

Page 29

background image

RA 19-4C 121013

2-11

2.4.2.2

GROUP CONTROL

Group control using one power supply designated as the master requires that the power supply
designated as the master be adjusted to the desired output voltage. All the other parallel-con-
nected units are slaves that track the output voltage of the master. This configuration can be
used to provide easy control of output bus voltage, however it is not truly redundant, since a fail-
ure of the master will cause a failure of the parallel-connected system. Failure of a slave
reduces the current capacity of the system, but it will continue to function.

For group control requiring a redundant system Kepco recommends configuring all parallel con-
nected units as slaves (see Table 2-3) controlled by a remote voltage. To eliminate a single point
failure possibility the remote voltage should have a backup and be connected in parallel to more
than one I/O connector.

At the rack adapter I/O connector use a shielded wire 6.6 feet (2M) maximum in length, for con-
nection of REF (pin 15), RV (pin 18), and –COM (pin 12) to the trimmer control or external volt-
age source (see Figure 2-7 or 2-8).

2.4.2.3

PARALLEL, MASTER SELECTED BY USER, SUPPLYING BALANCED CURRENT TO A
SINGLE LOAD

NOTE: For HSF 300W and 600W models, refer to associated power supply Operator Manual

for minimum load or output voltage limits needed to avoid “slave idle” or output oscilla-
tion (when slave is idle, output is off, no lights are lit, and alarm is set).

Figure 2-7 shows the connection of three power supplies in parallel to a single load. The output
voltage of all slave power supplies tracks the master. The master and slaves are determined by
the internal DIP switches, SW1 and SW2, of the HSF modules as defined in Table 2-3.

This configuration requires that CB (Current Balance) and RV (Remote Voltage) of all modules
be tied together, using either the DIP switches at the rear of the rack adapter, as shown in Figure
2-7, or by wiring the I/O mating connector as shown in Figure 2-8. Wiring of the I/O mating con-
nector allows non-adjacent slots to be connected in parallel.

TABLE 2-3. HSF DIP SWITCH CONFIGURATION FOR GROUP CONTROL

(ALLOWS MASTER TO CONTROL OUTPUT WHILE SLAVES TRACK MASTER)

MASTER

OR

SLAVE

HSF DIP
SWITCH

POSITION
(See Note)

HSF 300W, 600W

HSF 1200W, 1500W

Vadj Control

External R or V

Vadj Control

External R or V

SW2

SW1

SW2

SW1

SW2

SW1

SW2

SW1

MASTER

Position 1 (REF)

OFF

ON

ON

OFF

OFF

ON

ON

OFF

Position 2 (RV)

ON

ON

ON

OFF

ON

ON

ON

OFF

Position 7 (COM)

OFF

See

Note (2)

OFF

See

Note (2)

ON

ON

ON

See

Note (2)

SLAVE

Position 1 (REF)

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

Position 2 (RV)

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Position 7 (COM)

OFF

See

Note (2)

OFF

See

Note (2)

ON

OFF

ON

OFF

NOTES:
(1) HSF DIP Switches are located at the rear of each HSF module; refer to appropriate HSF manual for location.
(2) For HSF 600W, set SW1 position 7 to OFF

For HSF 300W, SW1 position 7 allows the DC ON indicator to powered by an internal auxiliary supply (see HSF

300W Operator Manual for details).