Retrotec FanTestic Customized Reports User Manual
Page 58
rev-2014-10-27
Page 58 of 61
©Retrotec Inc. 2011-2014
computer, power it off, turn it back on
after 10 seconds, and re-plug it back in.
Try the
button once
more.
Try plugging the DM-2 into an active
powered USB hub (with hub plugged into
mains power)
Cannot find gauges using DM-2 with firmware
older than version 3.0 (The version is displayed
when you turn on the DM-2 gauge, and on the
top line when you push [Setup].)
Any DM-2 gauge that is older than
Firmware Version 3.0 requires an Active
Powered USB HUB, with hub plugged into
mains power.
Find Gauges with DM-2 gauges results in a
message containing the phrase “Error 5: Access
Denied”
You must run FanTestic as Administrator
See the document:
Intermittent DM-2 connection over USB
Try plugging the DM-2 into an active
powered USB hub (with hub plugged into
mains power)
Try running both the laptop and the DM-2
from batteries, not plugged into any
external power source
If after doing an update or install, you get the
following notification:
This means that you had a previous version of
FanTestic that was set up to “Run as
Administrator”, likely to allow connection to the
DM-2 gauges for automatic control over the USB
port.
Click ok on the error, delete the old
ADMIN shortcut and
create a new shortcut as described in the
need to control DM-2 gauges
use the newly created shortcut if you are
not using DM-2 gauges
Unable to find gauges with DM32 connected to
USB port of laptop
Try plugging the DM32 into an active
powered USB hub (with hub plugged into
mains power). Some new laptops do not
provide enough power on the USB port.