Modbus operating modes – Precision Digital PD6730X User Manual
Page 9

PD6730X Vantageview Super Snooper Modbus Scanner
Instruction Manual
9
INPUT POWER
9-30 VDC, 38mA max. 2.2 W.
DATA LOGGING
Up to 511 records, recorded 4/day at specific times or at defined time intervals.
Record contains first eight enabled Modbus PVs; C1-4 if enabled; date; time;
pulse rate, total, and grand total with units; and log number.
ISOLATION
All Models:
500 V opto-isolated pulse input-to-power/OC output with
isolated input enabled.
500 V input/power-to-RS-485 serial communications
-AXA Models:
500 V input/power-to-analog output
ENVIRONMENTAL
Operating temperature range: -40 to 75°C
Storage temperature range: -40 to 75°C
Backlight deactivated below temperatures ≈ -20°C
Relative humidity: 0 to 90% non-condensing
NON-VOLATILE
MEMORY
All programmed settings and total reading are stored in non-volatile memory for a
minimum of ten years if power is lost.
CONNECTIONS
Screw terminals accept 12 to 22 AWG wire
ENCLOSURE
Injection-molded plastic with clear polycarbonate window, color: gray. NEMA 4X,
IP65. Material: polycarbonate with UV stabilizer. Default conduit connections:
Three ¾" NPT threaded conduit openings. Two ¾" NPT plastic plugs installed.
MOUNTING
May be mounted directly to conduit. Two slotted flanges for wall mounting or NPS
1½" to 2½" or DN 40 to 65 mm pipe mounting. See Mounting Dimensions on
page 97.
DISPLAY
ORIENTATION
Display may be mounted at 90° increments up to 270° from default orientation.
OVERALL
DIMENSIONS
5.67" x 5.25" x 4.18" (W x H x D)
(144 mm x 133 mm x 106 mm)
WEIGHT
1.65 lbs (26.4 oz, 0.75 kg)
WARRANTY
3 years parts and labor
Modbus Operating Modes
MASTER
Processes and displays data read from Modbus RTU slave devices. Up to 16
process variables (PVs) from up to 16 slave devices. Each PV programmed
individually.
SLAVE
Processes data sent to it from a Modbus RTU master device.
Note: Refer to Modbus Register Tables at www.predig.com for details.
SNOOPER
Listens to the Modbus traffic and picks up a specific register or registers being
polled by a Master device from a specific slave device and processes the data
being read. Up to 16 process variables (PVs) from up to 16 devices. If multiple
registers are polled by the master with one command, only the first returned
value will be read.
MASTER POLL TIME
0.1 to 99.9 sec. Time between read-commands.
MASTER TIMEOUT
0.1 to 99.9 seconds. Time elapsed after a poll request is made before the
scanner considers that request to have failed.
NUMBER OF RETRIES 1-99. The number of retries the scanner will make when requesting data before
reporting an error condition on the PV.
SNOOPER
RESPONSE TIME
0.1 to 99.9 seconds. Time since the last PV update the before being
considered an error.
SLAVE TIMEOUT
0.0 to 99.9 seconds. Time elapsed after the last data received from a master
before the scanner considers the data to be out of date. Programming 0
disables the timeout, and PV data will be displayed indefinitely despite not
being updated regularly.