IMPORTANT
Did you forget the passwords?
The password may be disabled by entering a master password. If you are authorized to
make changes, enter the master settings lockout (PASS) password 50865, the master
total reset (PASS T) password 80034, or the master grand total reset (PASS GT)
password 80034 to unlock the scanner.
Non-Resettable Grand Total
The grand total may be configured to be a non-resettable grand total. This is a permanent setting.
Configuring the grand total as a non-resettable grand total locks out all setup parameters that could be
used to reset the grand total or change the setup of the grand total; including pulse input selection, rate
scaling, and conversion factors.
To configure the meter for non-resettable grand total mode, enter the non-resettable grand total password
below into the Pass GT (PASS GT) parameter in the Password (PASS) menu.
The non-resettable grand total permanently locks the following parameters from being changed: pulse
input selection, K-factor, K-factor units, grand total units, grand total conversion factor, grand total decimal
point, scaling, calibration, grand total alarms, pulse input filter, and cutoff.
CAUTION
Locking the meter into a non-resettable grand total is not reversible. It is a permanent
meter configuration. Doing so will permanently prevent most pulse input parameters
from being altered. This should be the last step after verifying all setup parameters.
Non-resettable grand total password: 50873
Non-Resettable Grand Total Locked Menus & Parameters
Display
Parameter/Menu
Action/Setting Locked
PULSE
.IN
Pulse Input
All Pulse Input type selection menu parameters
GTOT U
Grand Total Units
Set grand total units
GT-CF
Grand Total Conversion Factor
Enter the Grand Total Conversion Factor menu
GRTOT.DP
Grand Total Decimal Point
Enter the grand total display decimal point
KFACTOR
K-Factor
All K-Factor menu parameters
sCalE
Scale
All Scale menu parameters
Pass GT
Password Grand Total
Enter the grand total reset password
GRTOT
Grand Total Alarm
All grand total alarm output menu parameters
FILTER
Filter
Enter Filter parameter
CUTOFF
Low-Flow Cutoff
Enter Low-Flow Cutoff parameter
The above menus remain accessible; however the parameters listed above within the menus are locked