PD6730X Vantageview Super Snooper Modbus Scanner
Instruction Manual
11
PARAMETER
SELECTION
Parameter 1 (PAR1), parameter 2 (PAR2), and parameter 3 (PAR3) selectable
as: Modbus PV1-16, math channel C1-4, pulse input rate, total, grand total, or
any math function.
PARAMETER
NESTED MATH
Defining parameter 1 or 2 as a math function will prompt for level 2 parameter 1
(L2P1), level 2 parameter 2 (L2P2), and/or level 2 parameter 3 (L2P3). Level 2
parameters function identically as parameter 1 and 2 for nested math functions.
Pulse Input
PULSE/
TRANSISTOR/
CONTACT CLOSURE
INPUT
Field selectable; Sourcing or sinking pulse or square wave
0-5 V, 0-12 V, or 0-24 V; TTL; NPN or PNP transistor;
Open collector 100 kΩ pull-up to 3 V;
Switch contact 100 kΩ pull-up to 3 V;
PNP transistor 100 kΩ pull-down to ground (COM)
Active input 100 kΩ to battery level, 10 kΩ to power
Maximum Frequency: 64 kHz
Minimum Pulse Width: 5 µs
Threshold Setting
Low (V) High (V)
Normal 1.2 2.0
Low 0.2 1.2
OPTO-ISOLATED
INPUT
Sourcing pulse or square wave 0-5 V, 0-12 V, or 0-24 V; Logic High: 2-24 V,
Logic Low: < 1 V
Maximum Frequency: 20 kHz
Minimum Pulse Width: 20 µs
Input Current: 1 mA @ 5 V, 2.5 mA @ 12 V, 5 mA @ 24 V
LOW VOLTAGE MAG
PICKUP INPUT
Sensitivity: 20 mVp-p to 24 Vp-p
Maximum Frequency: 6 kHz
MINIMUM INPUT
FREQUENCY
0.0001 Hz. Minimum frequency is dependent on high gate setting (rate display).
INPUT
IMPEDANCE
Pulse input: Greater than 75 k
@ 1 kHz.
Open collector/switch input: 100 k
pull-up to 3 V.
ACCURACY
±0.03% of calibrated span ±1 count
PULSE INPUT
RECALIBRATION
All ranges are calibrated at the factory to read frequency in Hz. No recalibration
required.
TEMPERATURE
DRIFT
Rate display is not affected by changes in temperature.
LOW-FLOW CUTOFF 0-99,999 (0 disables cutoff function)
DECIMAL POINT
Up to four decimal places or none:
4.4444
, 33.333, 222.22, 1111.1, or 00000
CALIBRATION
May be calibrated using K-Factor, scale without signal source, or by applying an
external calibration signal.
K-FACTOR
Field programmable K-Factor converts input pulses to rate in engineering units.
May be programmed from 0.000001 to 9,999,999 pulses/unit.
CALIBRATION
RANGE
Input 1 signal must be ≥ 1 Hz; input 2 signal may be set anywhere above input 1
setting. Minimum input span is 1 Hz.
An Error message will appear if the input 1 and input 2 signals are too close
together.
INPUT CONTACT
DEBOUNCE FILTER
Programmable contact debounce filter. Input signal frequency speed selections
of Hi (no filter), Med (250 Hz max input, 2 ms pulse width), and Low (100 Hz max
input, 5 ms minimum pulse width).
TIME BASE
Second, minute, hour, or day
GATE
Low gate: 1-99 seconds; High gate: 2-9,999 seconds