Precision Digital PD6730X User Manual
Page 73

PD6730X Vantageview Super Snooper Modbus Scanner
Instruction Manual
73
The following diagram details setting the analog output when the source is configured to display on the
top display of a decimal display model.
The following diagram details setting the analog output when the source is configured to display on the
top display of a feet and inches display model.
The following diagram details setting the analog output when the source is configured to display on the
bottom display.
See Setting Numeric Values on page 24 for more information on programming the display and output
values.
Note 1: On decimal display models, enter the output value in mA. On feet and inches display models,
enter the output value in µA.
Note 2:The hundreds digit on the feet display does not display 0 as a seven-segment 0; instead 0 is
represented with three horizontal bars as shown.
CAUTION
Please note that when power is removed from the scanner, the analog output will drop
below 1 mA.
Consider this effect when designing any system using the 4-20 mA output.