Application examples – Precision Digital PD6730X User Manual
Page 25
PD6730X Vantageview Super Snooper Modbus Scanner
Instruction Manual
25
APPLICATION EXAMPLES
The following applications show how the scanner can be configured for common applications.
Example 1: Master Polling Multivariable Level Transmitters
In this application we have a system consisting of (4) MTS M-Series multivariable tank level gauges
connected to PD6730-AX0-I-2 displaying product level, interface level, and average temperature. The
PD6730X is setup for Master mode, and is polling the Modbus transmitters.
Note: As a tank level indicator displaying in units of feet, a PD6730-AX0-I-L could also be considered for
this application. This would display feet and inches in the upper display, and include a tank level indicator.
Example 1 Level Transmitter Setup, Register Numbers, & Process Variables
Serial Communications
Parameters
Tank 1
Transmitter
Tank 2
Transmitter
Tank 3
Transmitter
Tank 4
Transmitter
Address (Slave ID)
001
002
003 004
Baud Rate
4800 bps
4800 bps
4800 bps
4800 bps
Transmit Delay
50 ms
50 ms
50 ms
50 ms
Parity
None 1
None 1
None 1
None 1
Fixed Serial Data
Parameters
MTS M-Series Transmitter Data
Level Register
30001, 30002
Interface Register
30003, 30004
Ave Temp Register
30017, 30018
Data Type
Long Integer (2 registers), Binary, Signed
Byte Order
1234 (most significant digit register first)
The following table shows the PD6730X setup to work with the MTS M-Series gauges.