PELLET STOVES

Chapter 2

INSTALLATION AND USE MANUAL

page

13

Theoretical notion for installation

Technical service - Rights reserved MCZ GROUP S.p.A. - Reproduction prohibited

2

1

be protected by a grille, metal mesh or suitable guard, as long as

this does not reduce the area below the minimum.

be positioned in such a way as to be impossible to obstruct

It is not compulsory to connect the air intake directly

with the stove (so that it draws air directly from

outside), but it is essential at all events to ensure an

airflow of 50 cubic metres per hour by the use of a

hole of the dimensions given.
See standard UNI 10683.

2.5. CONNECTION OF SMOKE DISCHARGE PIPE

When making the hole for the passage of the smoke discharge pipe, it

is necessary to take into account the possible presence of flammable

materials. If the hole will be going through a wall made of wood or any

other material which is sensitive to heat, the INSTALLER MUST first

of all use the special wall union (diam.13cm 13cm minimum) and

properly insulate the pipe of the stove that passes through it, using

adequate insulation materials (thickness 1.35cm with minimum thermal

conductivity of 0.07 W/m°K).

The same is true if the stove pipe must run through vertical or

horizontal stretches passing in proximity (min.20cm) to the heat-

sensitive wall

As an alternative we recommend the use of insulated pipe, which can

also be used on the outside to avoid condensation.

The combustion chamber works in low pressure. The smoke duct for

the discharge of fumes will also be under low pressure when connected

to an efficient flue pipe as directed.

Pipes and unions with suitable gaskets must always

be used, to guarantee a hermetic seal.

All sections of the smoke duct must be inspectable and

removable to enable periodic internal cleaning. Tee

connectors with inspection caps should be used.

Position the stove bearing in mind all the instructions and

considerations above.

IMPORTANT!

All 90 degree changes of direction in the flue pipe

must be fitted with suitable tee connectors to allow

the possibility of inspection. (see accessories for

pellet stove)

It is absolutely prohibited to fit a grille on the end of

the discharge pipe, because it could lead to poor

running of the stove.

FOR CONNECTION TO THE FLUE PIPE, NOT MORE

THAN 2-3 METRES OF HORIZONTAL PIPE MUST BE

USED AND NOT MORE THAN THREE 90° CURVES

MUST BE USED

IT IS ALSO ADVISABLE NOT TO EXCEED 6 METRES IN

LENGTH WITH THE PIPE Ø 80 mm

Example of pellet stove installation

Rear view of a pellet stove

1) Combustion air intake
2) Smoke outlet

3-5 %

2 - 3 mt. MAX

H

>

4

m

t.

H

>

1

,5

m

t.