Important – MCZ Antares '03 User Manual
Page 17

Installation
When making the hole for the passage of
the smoke discharge pipe, it is necessary
to take into account the possible
presence of flammable materials. If the
hole will be going through a wall made of
wood or any other material which is
sensitive to heat, the INSTALLER MUST
first of all use the special wall union
(diam.13cm minimum) and properly
insulate the pipe of the stove that passes
through it, using adequate insulation
materials (thickness1.3—5cm with
minimum thermal conductivity of 0.07 W/
m°K).
The same is true if the stove pipe must
run through vertical or horizontal
stretches passing in proximity (min.20cm)
to the heat-sensitive wall
As an alternative we recommend the use
of insulated pipe, which can also be used
on the outside to avoid condensation.
Combustion air
intake ø 50
Smoke
outlet ø 80
Pipes and unions with suitable gaskets
must always be used, to guarantee a
hermetic seal.
All sections of the smoke duct must be
inspectable and removable to enable
periodic internal cleaning. Tee connectors
with inspection caps should be used.
Position the stove bearing in mind all the
instructions and considerations above.
Important
All 90 degree changes of direction in
the flue pipe must be fitted with
suitable tee connectors to allow the
possibility of inspection (see the pellet
stove accessory list).
It is absolutely unacceptable to fit a
grille on the end of the discharge pipe,
because it could lead to poor running
of the stove.