World class 3000, Installation, Instruction manual – Emerson Process Management 3000 User Manual
Page 167
Instruction Manual
Appendix J Rev. 1.1
June 1995
Rosemount Analytical Inc. A Division of Emerson Process Management
Appendices J-3
World Class 3000
INSTALLATION
J-4
HART COMMUNICATOR SIGNAL LINE
CONNECTIONS
The HART Communicator can connect to the
IFT analog output signal line at any wiring ter-
mination point in the 4-20 mA current loop.
There are two methods of connecting the HART
Communicator to the signal line. For applica-
tions in which the signal line has a load resis-
tance of 250 ohms or more, refer to method 1.
For applications in which the signal line load re-
sistance is less than 250 ohms, refer to
method 2.
a. Method 1, For Load Resistance > 250
Ohms
Refer to Figure J-2 and the following steps
to connect the HART Communicator to a
signal line with 250 ohms or more of load
resistance.
R
250
L
>_
W
LOOP CONNECTORS
USE INTERFACE
00275 0013 ONLY
SERIAL PORT & BATTERY
CHARGER MUST
NOT BE USED IN
HAZARDOUS AREAS
SERIAL PORT
INTELLIGENT FIELD
TRANSMITTER IFT 3000
J1
JM1
JM6
J2
J3
J4
J5
J6
J7
J8
J9
I
V
MICROPROCESSOR
BOARD
CURRENT/VOLTAGE SELECTION SWITCH
TO "CURRENT" POSITION
INTERCONNECT BOARD
ANALOG OUTPUT
4-20mA SIGNAL LINE
ANALOG OUTPUT DEVICE
LEAD SET
HART
COMMUNICATOR
HART COMMUNICATOR
REAR PANEL
LOOP CONNECTORS
686002
Figure J-2. Signal Line Connections, > 250 Ohms Load Resistance
J