MPS 3000 TROUBLESHOOTING

D-3 OVERVIEW

This section describes troubleshooting for the
Multiprobe Calibration Gas Sequencer. Addi-
tional troubleshooting information can be found
in the Instruction Bulletin for the electronics
package.

Install all protective equipment covers
and safety ground leads after trouble-
shooting. Failure to replace covers
and ground leads could result in seri-
ous injury or death.

D-4 TROUBLESHOOTING

Table D-2 provides a guide to fault finding fail-
ures within the MPS. The flowchart in Figure
D-5 pr
ovides an alternate approach to fault
finding MPS related problems.

Table D-2. Fault Finding

SYMPTOM

CHECK

FAULT

REMEDY

1. Power to solenoid,

calibration gas not
released to probe.

Calibration gas

Insufficient calibration
gas

Install new calibration gas
tanks.

Solenoid

Solenoid failure

Replace solenoid.

2. No power to

solenoid.

Power supply output

Power supply failure

Replace power supply.

Fuses in power
supply

Fuse blown

Replace fuse.

Main power source

Main power off

Reestablish power.