5.0 Operation

Full Charge appears on LCD. PWR

(green) LED is on solid, and CHG

(green) LED blinks. FAULT (red) LED

is off, and INV (green) LED could be

on or off.

FAULT

PWR

CHG

INV

Full Charge

Settings/Info..

Figure 5-13, Full Charge Mode

• Full

Charge – This status indicates that you have entered the Battery

Saver™ mode. This mode maintains the batteries without overcharging, thus

preventing excessive loss of water in fl ooded batteries or drying out of GEL/

AGM batteries. After 4 hours Float Charging, the charger will turn off and “Full

Charge” is displayed (charger is now in Battery Saver™ mode). If the battery

voltage drops to ≤12.6 (12-volt models), ≤25.2 (24-volt models) or ≤50.4

(48-volt models), the charger will automatically initiate another 4 hours of

Float Charging. This cycle helps to ensure the batteries are monitored and

maintained, and continues as long as AC power is continuously connected

to the AC input.

Load Support AAC appears on LCD.

PWR (green) LED is on solid, and

CHG (green) LED blinks. FAULT (red)

LED is off, and INV (green) LED could

be on or off.

FAULT

PWR

CHG

INV

Load Support AAC

Settings/Info..

Figure 5-14, Load Support AAC Mode

• Load Support AAC – The inverter is in the Load Support (Amps AC)

mode because the inverter load is requiring more power than the incoming

AC source can provide on its own. The inverter pulls the additional current—

needed for the loads—from the inverter batteries to keep the incoming AC

current from exceeding the SHORE: Shore Max setting.

Info: The Load Support AAC feature operates in parallel with the

AC input to support the inverter loads and is only available on MSH

Series inverter/chargers. It is only active when the AC input is quali-

fi ed and connected, and the inverter is enabled (INV LED is on).

• Float

Charging

– At the end of the Absorb Charging time, the

charger reduces the charge voltage and tries to maintain the batteries at

the Float Charge voltage setting. This is determined by the SETUP menu’s

04 Battery Type setting as shown in Table 3-4.

Info: If the battery voltage falls ≤12.1 VDC (12-volt models), ≤24.2

VDC (24-volt models) or ≤48.4 VDC (48-volt models), the unit will

begin Bulk Charging.

Float Charging appears on LCD.

PWR (green) LED is on solid, and

CHG (green) LED is on solid, but may

blink. FAULT (red) LED is off, and INV

(green) LED could be on or off.

FAULT

PWR

CHG

INV

Float Charging

Settings/Info..