0 setup – Magnum Energy ME-RC Remote User Manual
Page 18

11
©2013 Magnum Energy, Inc.
3.0 Setup
Button
FEATURES/SETTINGS
Model/
Level
Required
Default
Setting
Main
Menu
Menu
Heading/Item
Selections/
Adjustments Range
SETUP
01
Search
Watts
Search= OFF, 5 - 50W
≥Level 1
5W
02 Low
Batt
CutOut
LBCO= 9.0 - 12.2 VDC*
≥Level 1
10.0 VDC
03
Absorb
Time
Absorb Hrs= 0.1 - 25.5 Hrs
≥Level 4
[4]
1.5 Hrs
04 Bat-
tery Type
BatType=
Gel, Flooded, AGM1, AGM2
≥Level 1
Flooded
Cus-
tom
[2]
Absorb =
(12.0 - 16.0V)*
≥Level 3
14.4V
Float =
(12.0 - 16.0V)*
13.2V
Equalize =
(12.0 - 16.0V)*
15.6V
CC/
CV
Max Amps =
(OFF, 20 - 990A)
≥Level 3
200A
Chg Volts =
(12.0 - 16.0V)*
13.8V
EndChg = (Time,
DC Amps, Hold
VDC)
Time
EndChg = Time
DoneTime =
(0.1 - 25.5 Hrs)
≥Level 4
[4]
1.5Hrs
MaxTime =
(OFF, 0.1-25.5)
12.0Hrs
Recharge =
(12.0-16.0V)*
12.0V
EndChg= DC Amps
DoneAmps =
(0 - 250ADC)
≥Level 4
20ADC
MaxTime =
(OFF, 0.1-25.5)
12.0Hrs
Recharge =
(12.0-16.0V)*
12.0V
Hold VDC
≥Level 1
14.6V
05
Charge
Rate
Max Charge=
0 - 100%
≥Level 3
80%
10 - 100%
≥Level 2
06 VAC
Dropout
Dropout=
US Models: 60 - 100
VAC, UPS Mode
≥Level 1
80 VAC
Export Models: 110 - 190
VAC, UPS Mode
≥Level 1
150 VAC