0 setup – Magnum Energy ME-RC Remote User Manual

Page 18

background image

11

©2013 Magnum Energy, Inc.

3.0 Setup

Button

FEATURES/SETTINGS

Model/

Level

Required

Default

Setting

Main

Menu

Menu

Heading/Item

Selections/

Adjustments Range

SETUP

01

Search

Watts

Search= OFF, 5 - 50W

≥Level 1

5W

02 Low

Batt

CutOut

LBCO= 9.0 - 12.2 VDC*

≥Level 1

10.0 VDC

03

Absorb

Time

Absorb Hrs= 0.1 - 25.5 Hrs

≥Level 4

[4]

1.5 Hrs

04 Bat-

tery Type

BatType=

Gel, Flooded, AGM1, AGM2

≥Level 1

Flooded

Cus-

tom

[2]

Absorb =

(12.0 - 16.0V)*

≥Level 3

14.4V

Float =

(12.0 - 16.0V)*

13.2V

Equalize =

(12.0 - 16.0V)*

15.6V

CC/

CV

Max Amps =

(OFF, 20 - 990A)

≥Level 3

200A

Chg Volts =

(12.0 - 16.0V)*

13.8V

EndChg = (Time,

DC Amps, Hold

VDC)

Time

EndChg = Time

DoneTime =

(0.1 - 25.5 Hrs)

≥Level 4

[4]

1.5Hrs

MaxTime =

(OFF, 0.1-25.5)

12.0Hrs

Recharge =

(12.0-16.0V)*

12.0V

EndChg= DC Amps

DoneAmps =

(0 - 250ADC)

≥Level 4

20ADC

MaxTime =

(OFF, 0.1-25.5)

12.0Hrs

Recharge =

(12.0-16.0V)*

12.0V

Hold VDC

≥Level 1

14.6V

05

Charge

Rate

Max Charge=

0 - 100%

≥Level 3

80%

10 - 100%

≥Level 2

06 VAC

Dropout

Dropout=

US Models: 60 - 100

VAC, UPS Mode

≥Level 1

80 VAC

Export Models: 110 - 190

VAC, UPS Mode

≥Level 1

150 VAC