3.0 Setup

Where should I set my Maximum Charge Rate? The maximum charge

rate is generally set to a C/5* rate (C = the total amp-hour capacity of the

battery bank—using the 20-hour AH rate). The C/5 rate is usually used when

the objective is to charge the batteries as quickly as possible (i.e., 400 AH ÷

5 = 80 amp maximum charge rate). A lower rate such as C/20* is used when

the batteries need to be charged as slow as possible.

CAUTION: The C/5 or C/20 charge rate settings are guidelines; they

are not requirements on how to set your battery charge rate. For spe-

cifi c charge rate requirements, refer to your battery’s manufacturer.
Info: If multiple inverter/chargers are used on a single battery bank,

you must ensure that the total charge rate from all inverter/char-

gers is limited to the maximum charge rate needed for your battery

bank. The maximum Charge Rate setting only limits the charging

on each inverter/charger individually, not on all inverter/chargers.

* C/5 or C/20 rate – charge rates are commonly expressed as a ratio of the total

amp-hour (AH) capacity of the battery bank. For example, with a 400 AH battery

bank (C = 400), the C/5 charge rate is 80 A (400/5 = 80 A).

Press to save

SETUP

Press

Status...

05 Charge Rate

Rotate to

Press to select

Rotate to

desired

selection:

Range: 0-100% (increments 10%)

Figure 3-12, SETUP: 05 Charge Rate Selections

• SETUP: 05 Charge Rate Sets the maximum charge rate allowed

to charge the batteries during Bulk, Absorption, Float, and Equalize

charging. The Max Charge = 0% setting helps minimize charging

while continuing to allow pass-thru power. The rest of the selections

are provided to limit the charge rate to the battery bank, which helps

prevent battery overheating caused by charging at too high a charge rate.
The Max Charge selections are provided as a percentage of the inverter/

charger’s maximum charging capability. Refer to the label on the side of

the inverter (or owner’s manual) to determine the inverter’s maximum

charge rate. Once you fi nd this maximum charge rate, determine the

percentage needed to limit the charge rate to your battery bank.
Default setting: Max Charge = 80%
Range: 0-100%

Note: If “CC/CV Controlled” displays on this menu’s screen, you will not be

able to adjust the settings as “CC/CV” has been selected as the battery type

from the 04 Battery Type menu.
Example
: The maximum charge rate of your inverter/charger is 120

amps and you need to limit the charge rate to 72 amps. Choose the

Max Charge = 60% setting (72 amps = 60% of 120 amps)

.

Info: If Max Charge = 0%, the topology of the inverter—when

connected to an AC source—will override the 0% setting and start

charging if the battery voltage is <11 VDC (12v models), <22 VDC

(24v models), or <44 VDC (48v models).