beautypg.com

5 tech menu, 0 setup – Magnum Energy ME-RC Remote User Manual

Page 36

background image

29

©2013 Magnum Energy, Inc.

3.0 Setup

3.3.5 TECH

Menu

The TECH menu button provides access to selections that are used to

assist service technicians in troubleshooting. It provides access to system

information along with a selection that allows all system settings to be

returned to the original factory default values.

TECH: 01 Temperatures – Displays the various temperatures measured

throughout the system. Rotate the SELECT knob to scroll through these

temperature readings. The following read only temperature displays are

available:
BTS: Displays temperature of the inverter’s Battery Temp Sensor

(BTS)—if one is connected to the battery bank.
Tfmer: Displays temperature of the main power transformer (Tfmer)

inside the inverter.
FETs: Displays temperature of inverter’s Field Effect Transistors (FETs).
AGS: Displays the temperature of the AGS temp sensor—if one is

connected. If no AGS is connected, “No Comm” displays.

• SETUP: 10 Pwr Up Always – Allows the inverter to power up and

provide AC power automatically once DC voltage is connected to the

inverter.
Default setting: Pwr Up = NO
Range: YES, NO

What is the Power Up Always feature? Normally, when DC power is

connected to the inverter, the user is required to press the power button—on

the inverter or remote—to turn the inverter on. When the Power Up Always

feature is activated by selecting YES, the inverter is automatically turned

on and starts searching or inverting—depending on the 01 Search Watts

setting. Once the inverter has connected to DC power and is automatically

turned on, the power button—on the inverter or remote—can be used to turn

the inverter on or off.
Why use the Power Up Always feature? Some customers are familiar

with Uninterruptible Power Supplies (UPS) that power-up automatically

when DC power is connected. The Power Up Always feature can be used by

customers that want to obtain the same automatic power-up feature with

which they are familiar.

mode, the charger again transitions to Silent mode. This silent to rebulk

to absorb and back to silent cycle will continue as long as it is required.
ReBulk – When Silent is selected, you must also set the DC voltage

set-point where the charger restarts the Bulk Charge mode. This setting

should be at the lowest DC volts you want the batteries to fall before

starting a new bulk charge. Typically, the lowest DC volts the batteries

are allowed to fall is 12.0 to 12.2 VDC (12-volt systems), 24.0 to

24.4 VDC (24-volt systems), and 48.0 to 48.8 VDC (48-volt systems)

respectively.
Default setting: Rebulk = 12.0V (for 12v inverter)
Ranges: 12.0-16.0 VDC (12v), 24.0-32.0 VDC (24v), 48.0-64.0 VDC (48v)

Why should I use the Silent Stage? Silent mode is typically used when

an alternate charge source is available and able to fully charge or fi nish the

charge cycle after the Absorb stage. A major difference between Multi mode

and Silent mode is that the Silent mode returns to Bulk mode instead of Float

mode. In Silent mode you can also adjust the Rebulk set-point in order to

allow the alternate charge source to provide more of the battery charging.