3.0 Installation
DC8A
DC6
DC1
DC2
DC4
DC7
DC5
DC3
DC8B
Figure 3-23, DC Wiring Connection Points for MPDH-30D (DC Side)
DC N
EGATIVE
C
ABLE
C
ONNECTIONS
TO
I
NVERTER
A
DDITIONAL
I
NVERTER
DC
N
EGATIVE
C
ABLE
C
ONNECTIONS
DC G
ROUNDING
E
LECTRODE
C
ONNECTIONS
B
ATTERY
B
ANK
P
OSITIVE
C
ABLE
C
ONNECTIONS
A
DDITIONAL
B
ATTERY
B
ANK
N
EGATIVE
C
ABLE
C
ONNECTIONS
DC P
OSITIVE
C
ABLE
C
ONNECTIONS
TO
I
NVERTER
DC E
QUIPMENT
G
ROUNDING
C
ONNECTIONS
B
ATTERY
B
ANK
N
EGATIVE
C
ABLE
C
ONNECTIONS
DC C
ONNECTIONS
(
UNDER
THE
DC D
ISCONNECT
)
I
NVERTER
DC C
ONNECTIONS
(I
N
AC S
IDE
)
DC1
Inverter’s DC Negative Cable Connections - Cable connections to Magnum inverter’s
DC negative terminal. Electrically connected to the top of the DC shunt.
DC2
Inverter’s DC Positive Cable Connections - Cable connections to Magnum inverter’s
DC positive terminal. Electrically connected to the top of the inverter’s DC disconnect.
DC3
Additional Inverter DC Negative Cable Connections - Provided so that as more invert-
er’s are added, cables can be added and connected to the inverter’s DC negative terminals.
DC4
Battery Bank Negative Cable Connections - DC negative busbar connections (bottom
connection of DC shunt); connect cables to the battery bank’s negative terminal.
DC5
Additional Battery Bank Negative Cable Connections - Provided to connect
additional cables to the battery bank’s negative terminal when additional Magnum
inverters are installed.
DC6
Battery Bank Positive Cable Connections - Bottom of the inverter’s DC disconnect
breaker; connect battery cables to the battery bank’s positive terminal.
DC7
DC Equipment Grounding Connections - These busbars are used as the common
DC equipment ground point for all DC equipment connected in the MP/inverter system.
DC8
DC Grounding Electrode Connections - These are the connection points for the MP/
inverter system to the DC grounding electrode. Use DC8A for #6 to #1/0 AWG wires,
and DC8B for greater than #1/0 AWG wires.