Mp enclosure, Dc side ac side, 0 operation – Magnum Energy Magnum Panel (MP Series) User Manual
Page 100
© 2011 Magnum Energy, Inc.
Page 93
5.0 Operation
5.0 Operation
The MP enclosure provides you with
circuit
breakers/disconnects to easily operate and maintain
your inverter/battery system. These breakers
are used as the main power disconnecting means
and/or overcurrent protection. Refer to Figure 5-1 to view a simple diagram of the
functional
operation of the breakers within the MP enclosure.
Info: Figure 5-1 is for descriptive purposes only, for specifi c wiring directions please
refer to the relevant wiring diagram in the Installation section of this manual.
Info: For information on operating the inverter, refer to its owner’s manual.
If a short-circuit condition occurs, or if a load is placed on the circuit breaker that is more than its
rated capacity, the breaker will trip OFF (down). On the AC breakers, a red indicator will display
through the clear window on the circuit breaker to show a tripped condition. On the other circuit
breakers, the handle will trip all the way to the OFF position.
Before resetting the breaker, fi rst determine the cause of the overcurrent fault. Then, reset the
circuit breaker by turning it all the way OFF, and then all the way back ON. For proper maintenance
and longer life, the circuit breakers should be turned off and on several times at least once a year.
This will help to prevent the contacts inside from sticking together.
To shut the MP/inverter system OFF completely, all of the circuit breakers in the MP
enclosure must be switched to the OFF position.
Figure 5-1, MP Functional Diagram
AC Input Busbars
AC IN
AC OUT
AC
OUTPUT
AC
INPUT
INVERTER
(AC side)
AC Output Busbars
INV IN
INV OUT
AC INPUT
Breakers
DC Side
AC Side
MP Enclosure
AC
SOURCE
FROM MAIN
PANEL
(Customer
Connection)
DC
INPUT
INVERTER
(DC side)
DC Shunt
DC NEG Busbar
DC POS Busbar
INV DC Breaker
BATTERY
BANK
(Customer
Connection)
NEG (-)
POS (+)
AC BYPASS AC OUTPUT
ON
OFF
ON
OFF
DC
LOADS
(Customer
Connection)
DC
Breakers
(optional)
AC
LOADS
IN SUB-
PANEL
(Customer
Connection)