beautypg.com

A-1 inverter/charger specifi cations, Appendix a – specifi cations, Models – Magnum Energy MS Series User Manual

Page 64

background image

©

2012 Magnum Energy, Inc.

Page 55

Appendix A – Specifi cations

Models

MS2000/MS2012

MS2812

MS2024

MS4024

Inverter Specifi cations

Input battery voltage range

9.0 to 16.8 VDC

18.0 to 33.6 VDC

Absolute maximum DC input

25 VDC

35 VDC

AC output voltage accuracy

120 VAC ±5% (≤ continuous power)

Output frequency and accuracy

60 Hz ± 0.1 Hz

Total Harmonic Distortion (THD)

< 5%

Continuous power output (at 25°C)

2000 VA

2800 VA

2000 VA

4000 VA

Continuous AC output current

17 A

23 A

17 A

33 A

1 msec surge current (amps AC)

50

70

75

120

100 msec surge current (amps AC)

33

40

37

82

5 sec surge power (real watts)

3300

3900

2850

5800

30 sec surge power (real watts)

3100

3800

2750

5400

5 min surge power (real watts)

2800

3200

2700

4900

30 min surge power (real watts)

2200

3000

2200

4500

Maximum continuous input current

267 ADC

373 ADC

133 ADC

267 ADC

Inverter effi ciency (peak)

90.6%

90%

86%

93.7%

HBCO/HBCI (High Battery Cut Out/In)

16.8 VDC/16.5 VDC

33.6 VDC/33.0 VDC

LBCO/LBCI (Low Battery Cut Out/In)

9.0 VDC (adj)/12.5 VDC

18.0 VDC (adj)/25.0 VDC

Series Stacking for 120/240 VAC

No

Yes, using two MS4024s

AC Relay Transfer time (minimum)

16 msec

Power Consumption - searching

<8 watts

Power Consumption - inverting (no load)

25 watts

30 watts

25 watts

Output Waveform

Pure Sine Wave

Charger Specifi cations

Continuous charger output at 25°C

100 ADC

125 ADC

60 ADC

105 ADC

Input current for continuous rated output

15 AAC

18 AAC

7.9 AAC

29 AAC

Charger effi ciency

85%

AC input frequency range

50 to 70 Hz

AC input voltage range

60 to 140 VAC (120 VAC nominal)

Power factor

> 0.95

General Features and Capabilities

Transfer relay capability

30AAC maximum each input (30AAC total on MS2000 models, 60AAC total on all other models)*

Five-stage charging capability

Bulk, Absorb, Float, Equalize (requires remote), and Battery Saver™

Battery temperature compensation

Standard with available temp sensor connected (battery temp 0 - 50 °C)

Internal Cooling

0 to 120 cfm variable speed drive using dual 92 mm brushless DC fan

Overcurrent protection

with two overlapping circuits

Over-temperature Protection

on transformer, MOSFETS, and battery

Corrosion protection

PCB’s conformal coated, powder coated chassis/top, and stainless steel fasteners

Safety Listings

ETL listed to UL/cUL 458, UL 1741, CSA C22.2 No. 107.1-01, and meets KKK-A-1822E standard**

Warranty

3 years parts and labor

Branch-rated output circuit breakers

Optional on MS2000 (15 or 20 amp breakers) or MS2012 (15 or 20 amp breakers)

Environmental Specifi cations

Operating temperature

-20°C to +60°C (-4°F to 140°F)

Non-Operating temperature

-40°C to +70°C (-40°F to 158°F)

Operating humidity

0 to 95% RH non-condensing

Physical Specifi cations

Unit Dimensions (length x width x height)

13.75” x 12.65” x 8.0” (34.9 cm x 32.1 cm x 20.3 cm) [Height on MS2000 models is 7.0”/17.8 cm]

Shipping Dimensions (length x width x height)

19” x 17” x 13” (48.3 cm x 43.2 cm x 33 cm)

Mounting

Shelf or wall (vents not allowed to face downward unless ME-CB or MMP/MP is installed)

Unit Weight

42 lb (19.1 kg)

55 lb (24.9 kg)

41 lb (18.6 kg)

55 lb (24.9 kg)

Shipping Weight

50 lb (22.7 kg)

63 lb (28.6 kg)

49 lb (22.2 kg)

63 lb (28.6 kg)

Max operating altitude

15,000’ (4570 m)

* The pass-thru capability on each leg of the -15B and -20B models is limited by the output breaker size on each output.
** MS2000 models

ETL listed to UL/cUL 458, CSA C22.2 No. 107.1-01, and meet KKK-A-1822E standard. MS2024 model not listed to UL/CSA stds.

Specifi cations @ 25°C - Subject to change without notice.

Appendix A – Specifi cations and Optional Equipment

A-1 Inverter/Charger

Specifi cations

This manual is related to the following products: