Installation

2.5.6

AC Wiring Confi gurations (MS2012, MS2812, MS2024, MS4024)

The following table provides the different wiring confi gurations for installing and connecting the AC

conductors to and from the inverter (refer to Figures 2-9 to 2-13 for installation drawings showing

these confi gurations). Refer to Table 2-4 (and Figures 2-14 & 2-15) for the MS2000 models.

Table 2-3, AC Input/Output Wiring Confi gurations

SI/SO

(30A)

Single In/

Single Out

(30A)

SI/SO (60A)

Single In/

Single Out

(60A)

SI/DO

Single In/

Dual Out

DI/SO

Dual In/Single

Out

DI/DO

Dual In/

Dual Out

AC Source

1

Required

120 VAC @ <

30 amps

120 VAC @ >

30 amps

(60 amps

maximum)

120/240 VAC (or

2 separate legs of

120 VAC)

@ < 15 amps per

leg (-15B models);

or < 20 amps per

leg (-20B models).

120/240 VAC (or

2 separate legs

of 120 VAC)

@ < 30 amps

per leg

120/240 VAC (or

2 separate legs

of 120 VAC)

@ < 30 amps per

leg

Reason to

Use

Have an 120

VAC source

that is < 30

amps.

Requires

a separate

inverter

sub-panel.

Have an 120

VAC source

that is > 30

amps.

Requires

a separate

inverter

sub-panel.

Do not want to

install a separate

inverter sub-panel.

Inverter pass-thru

capability limited

on each leg by

model used.

Want dedicated

charging and

dedicated pass-

thru while the

AC source is on.

Requires a

separate inverter

sub-panel.

May need to

power 240 VAC

loads when

AC source is

on (requires

120/240 VAC

source).

Requires a

separate inverter

sub-panel.

Appropriate

Models

MS2012

MS2812

MS2024

MS4024

MS2012

MS2812

MS2024

MS4024

MS2012-20B

MS2012-15B

MS2012

MS2812

MS2024

MS4024

MS2012

MS2812

MS2024

MS4024

Maximum

Input

Breaker

Required

-

Minimum

Wire Size

(AWG)

30A

(single pole)

-

#10 AWG

(In & Out)

60A

(single pole)

-

#6 AWG

(In & Out);

Can be split to

two #10 AWG

(for HOT 1

& HOT 2)

For full charging

and pass-thru

-15B=45A SP

-20B=60A SP

-

-15B In=#8

(split to #12 x2)

-20B In=#6

(split to #10 x2)

-15B Out=#12 x2

-20B Out=#10 x2

30A

(dual pole)

-

#10 AWG

(In & Out)

30A

(dual pole)

-

#10 AWG

(In & Out)

Maximum

Inverter

Pass-thru

capacity

3600W

(30A @ 120

VAC)

7200W

(60A @ 120

VAC)

-15B models:

15A/leg

(30A max.);

-20B models:

20A/leg

(40A max.)

3600W

(30A @ 120

VAC)

7200W

(2 legs of 30A @

120/240 VAC or

2 legs of 30A @

120 VAC)

2

Wiring

Diagram

Figure 2-9

Figure 2-10

Figure 2-11

Figure 2-12

Figure 2-13

Note

1

– AC Source is from either the utility/grid power (i.e., shorepower) or an AC generator.

Note

2

– If two legs of 30A @ 120 VAC are used, they must be from the same source (i.e., have a common

neutral).