Installation – Magnum Energy MS Series User Manual
Page 40

©
2012 Magnum Energy, Inc.
Page 31
Installation
2.5.8
AC Wiring Confi guration (MS2000 models)
The following table provides the different wiring confi gurations for installing and connecting the
AC conductors to and from MS2000 model inverters (see Figures 2-14 and 2-15 for installation
diagrams showing these confi gurations).
Table 2-4, AC Input/Output Wiring Confi gurations (MS2000 models)
SI/SO (30A)
Single In/
Single Out
(30A)
SI/DO
Single In/
Dual Out
AC Source
1
Required
120 VAC @
< 30 amps
120 VAC @
< 30 amps
@ < 15 amps per
leg (-15B models);
or < 20 amps per
leg (-20B models).
Reason to
Use
Have an 120
VAC source
that is < 30
amps.
Requires
a separate
inverter
sub-panel.
Do not want to
install a separate
inverter sub-panel.
Inverter pass-thru
capability limited
by model used.
Appropriate
Models
MS2000
MS2000-15B
MS2000-20B
Maximum
Input
Breaker
Required
-
Minimum
Wire Size
30A
(single pole)
-
#10 AWG
(In & Out)
-15B models:
30A (single pole);
-20B models:
30A (single pole)
-
#10 AWG (In)
#12 AWG x2 (Out)
Maximum
Inverter
Pass-thru
capacity
3600W
(30A @
120 VAC)
-15B models:
15A/leg
(30A max.);
-20B models:
20A/leg
(30A max.)
Wiring
Diagram
Figure 2-14
Figure 2-15