2.2 Mounting the Inverter

The inverter base can reach a temperature up to 90°C (194°F) and should be mounted on a

noncombustible surface*. This surface and the mounting hardware must also be capable of

supporting at least twice the weight of the inverter. To meet regulatory requirements, the MS

Series must be mounted in one of the following positions as shown in Figure 2-2:
• above or under a horizontal surface (shelf or table),
• on a vertical surface (wall) with the DC terminals to the right,
• on a vertical surface (wall) with the DC terminals toward the bottom, the MP-HOOD (inverter

hood) installed on the top, and either the ME-CB (Conduit box), MMP series (single inverter

enclosure), or MP Series (multiple inverter enclosure) installed on the inverter’s bottom.

Info: The ME-CB, MMP and MP Series enclosures prevent material from falling out the

bottom in the event of an internal fi re, and also allow suffi cient ventilation to prevent the

inverter from overheating under normal operating conditions. The MP-HOOD inverter

hood helps prevent items from falling inside causing damage to the inverter.
Info: Magnum provides a backplate for mounting the inverter. These backplates also

provide the ability to mount either the MMP Series enclosure (PN: BP-MMP) or the MP

Series Enclosure (PN: BP-S single plate, or BP-D dual plate).

After determining the mounting position, refer to the physical dimensions as shown in Figure

2-3, or use the base of the inverter as a template to mark your mounting screw locations. After

marking the mounting screw locations, mount the unit with appropriate mounting hardware.

* Noncombustible surface – A surface made of material that will not ignite, burn, support combustion, or

release fl ammable vapors when subjected to fi re or heat as per the ASTM E136 standard. For the most part,

these are materials that are largely comprised of inorganic materials such as stone, steel, iron, brick, tile,

concrete, slate, and glass. Avoid common building materials such as gypsum board as well as any paint, wall

coverings, and all types of wood.

Figure 2-2, Approved Mounting Positions

30

30

S

HELF

OR

T

ABLE

M

OUNTED

(

RIGHT

SIDE

UP

)

S

HELF

OR

T

ABLE

M

OUNTED

(

UP

SIDE

DOWN

)

W

ALL

M

OUNTED

(DC

TERMINALS

TO

THE

RIGHT

)

W

ALL

M

OUNTED

(DC

TERMINALS

FACING

DOWN

*)

*W

HEN

THE

INVERTER

IS

MOUNTED

IN

THIS

POSITION

,

THE

MP-HOOD

(

INVERTER

HOOD

ON

TOP

),

AND

THE

ME-CB

(

CONDUIT

BOX

ON

BOTTOM

)

OR

MP/MMP S

ERIES

E

NCLOSURES

MUST

BE

USED

.

This manual is related to the following products: