3 dc cable connections, Installation – Magnum Energy MS Series User Manual

Page 26

background image

©

2012 Magnum Energy, Inc.

Page 17

Installation

Table 2-2, DC Wire Size For Increased Distance

Inverter

Model

Minimum Recommended DC Wire Size (one way)*

5 feet or less

5 to 10 feet

10 to 15 feet

In Conduit

In Free Air

In Conduit

In Free Air

In Conduit

In Free Air

MS2000

#4/0 AWG

#2/0 AWG

#4/0 AWG x2

#4/0 AWG

not

recommended

#4/0 AWG x2

MS2012

#4/0 AWG

#2/0 AWG

#4/0 AWG x2

#4/0 AWG

not

recommended

#4/0 AWG x2

MS2812

#4/0 AWG

#4/0 AWG

#4/0 AWG x2

#4/0 AWG x2

not

recommended

not

recommended

MS2024

#1 AWG

#4 AWG

#1/0 AWG

#2 AWG

#2/0 AWG

#1/0 AWG

MS4024

#4/0 AWG

#2/0 AWG

#4/0 AWG x2

#4/0 AWG

not

recommended

#4/0 AWG x2

* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F).

2.4.3

DC Cable Connections

Do not put anything between the battery cable ring lug and the battery post or the fl at metal part

of the inverter’s DC terminal. When connecting the battery cable to the battery post or inverter

DC terminal, the cable should be placed directly against the inverter terminal or battery post.

Incorrectly installed hardware causes a high resistance connection which could lead to poor inverter/

charger performance, and may melt the cable and terminal connections.
Refer to Figures 2-5 and 2-6 to connect the DC cables and to stack the hardware correctly. Tighten

the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).

CAUTION: The DC terminal and Flange/Kep nuts are made of stainless steel which have

a high likelihood of seizure. To help prevent the bolt and nut from seizing—causing the

bolts to strip or snap/break-off—the use of anti-seize lubricant is highly recommended.

Info: If antioxidant grease or spray is used, apply it after all the connections have been

made and are properly tightened.

Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Flange/Kep nuts.

Figure 2-5, Battery Hardware

Installation

Figure 2-6, Inverter DC Hardware

Installation

battery cable

(with ring lug)

nut

split washer

flat washer

Battery

Temperature

Sensor

battery

post

CAUTION:

Ensure nothing is

placed between

the cable ring lug

and battery post.

5/16-18

Flange or

Kep nut

battery cable

(with ring lug)

Inverter DC terminal

(

5/16–18 bolt,

5/8" usable length

)

CAUTION:

Ensure nothing is

placed between the DC

terminal and ring lug.