Operation

3.8 Factory Default Values

Your MS Series inverter/charger uses default values for the adjustable settings (shown in Table

3-2) that are adequate for most installations. If some of your operating parameters need to be

changed from the default values, an optional remote control/display can be used to make those

changes. To help you determine if you need a remote display, information on the inverter/charger

settings that can be changed is provided below. The settings, once programmed, are saved in the

remote’s non-volatile memory and are preserved until changed—even if DC power to the inverter

is lost (as long as the remote is connected). For information on the full range of settings for each

function in your remote, refer to its owner’s manual at www.magnumenergy.com.

• Shore

Max/Input

Amps: This setting ensures the inverter AC loads receive the maximum

current available from the utility or generator power. When the total current used to power

the AC loads and charge the batteries begins to approach the Shore Max setting, the

current that was used for charging the batteries will automatically be reduced.

• Search

Watts: This setting allows you to turn off the power-saving Search mode circuitry,

or to adjust the power level at which the inverter will “wake up” and start inverting.

• LowBattCutOut:

This setting determines when the inverter will turn off based on low

battery voltage. The inverter turns off automatically after the battery voltage has been

below this setting for more than one minute. This protects the batteries from over-

discharge and the AC loads from unregulated power (brown-outs).

• Batt

AmpHrs/Absorption

Time:

This setting allows the user to input the battery bank

size in amp hours or to set the absorption time—which tells the charger how long to

charge the batteries in the Absorb Charge stage.

• Battery

Type:

Sets the type of batteries being used in the system. This information tells

the charger what voltage level to use to charge the batteries.

• Charge

Rate:

This setting can be used to turn off the charger, limit the amount of current

that the charger can use (leaving more current available to power loads), or to ensure

small battery banks are not overheated because of a charge rate that is too high.

• VAC

Dropout:

Sets the minimum AC voltage that must be present on the AC input before

the unit transfers from Standby mode to Inverter mode. This protects the AC loads from

utility outages and brown-outs.

Using a remote display also provides the following features:
• allows you control to enable an equalize charge for certain battery types

• displays inverter/charger’s operating status

• provides fault information for troubleshooting

Table 3-2, Inverter/Charger Default Values

Adjustable Settings

Default Values

Shore Max/Input Amps

30 Amps

Search Watts

5 Watts

LowBattCutOut

12v = 10 VDC (one min. delay), 8.5 VDC (no delay)

24v = 20 VDC (one min. delay), 17.0 VDC (no delay)

Batt AmpHrs/Absorption Time

600 AmpHrs (Absorb Time = 120 minutes)

Battery Type

Flooded – Liquid Lead Acid:

12V = Absorb 14.6 VDC, Float 13.4 VDC;

24V = Absorb 29.2 VDC, Float 26.8 VDC

Charge Rate

100%

VAC Dropout

80 VAC