Table 6, Inverter Default Settings

03 Battery AmpHrs: This setting allows you to input the battery bank

size in amp hours. This provides information to the charger on how

long to charge the batteries in the Absorb Charging stage.

04 Battery Type: This setting identifi es the type of batteries being

used in the system. This provides information to the charger to

determine what voltage level to use to charge the batteries.

05 Charge Rate: T

his setting can be used to turn off the charger, limit

the amount of current that the charger can use (leaving more current

available to power loads); or, to ensure small battery banks are not

overheated because of a charge rate that is too high.

06 VAC Dropout: Sets the minimum AC voltage that must be pres-

ent on the AC input before the unit transfers from Standby Mode to

Inverter Mode. This protects the AC loads from utility outages and

brown-outs.

The ME-RC50 remote also provides the following features:

allows you to enable an equalize charge for certain battery

types
displays the inverter/charger’s operating status
provides fault information for troubleshooting


3.0 Operation

31

Function

Default Settings

Search Watts

5W

LowBatCutOut

10.0 VDC (MM1524AE - 20.0 VDC)

Battery AmpHrs

400 AmpHrs

(Absorb Time = 120 minutes)

Battery Type

Flooded - Liquid Lead Acid

(Bulk = 14.6 VDC, Float = 13.4 VDC)

(MM1524AE - Bulk = 29.2 VDC, Float = 26.8 VDC)

Charge Rate

100%

VAC dropout

80VAC