Constant

Current

Reduced

Current

Reduced

Voltage

Absorb volts

‘Adj

Charge

Rate’

Setting

Increased

Voltage

Constant

Voltage

Monitored

Voltage

No Current

Time

Float

volts

Monitored

Current

Absorb Time

(d etermined b y

the ‘Ad j Batt

Amp H rs’ setting)

Bulk

Charging

Absorb

Charging

Float

Charging

DC

Voltage

DC

Current

Full

Charge

Goes to Full

Charge after 4

hours in Float

Charge

Absorb and Float voltage settings are

determined by the ‘Battery Type’ selection

Figure 12, Automatic 4-Stage Charging Graph

Transfer time - While in Standby Mode, the AC input is continually

monitored. Whenever AC power falls below the VAC dropout voltage

(80 VAC, default setting), the inverter automatically transfers back

to Inverter Mode with minimum interruption to your appliances – as

long as the inverter is turned on. The transfer from Standby Mode

to Inverter Mode averages approximately 16 milliseconds. While the

MM-AE Series is not designed as a computer UPS system, this transfer

time is usually fast enough to hold them up. However, the VAC dropout

setting has an effect on the ability of the loads to transfer without

resetting. The lower this setting, the longer the effective transfer

will be and therefore, the higher the probability for the output loads

to reset. This occurs because the incoming AC voltage is allowed to

fall to a level that is so low that when the transfer does occur, the

voltage on the inverter’s output has already fallen to a low enough

level to reset the loads.
The disadvantage of a higher VAC dropout setting is that smaller

generators (or large generators with an unstable output) may nui-

sance transfer. This commonly happens when powering loads that

are larger than the generator can handle – causing the generator’s

output voltage to constantly fall below the inverter’s input VAC drop-

out threshold.

Info: You must use the ME-RC50 remote to adjust the

VAC dropout setting – which in turn determines the VAC

dropout threshold.
Info: When switching from Inverter Mode to Standby

Mode, the inverter waits approximately 15 seconds to

ensure the AC source is stable before transferring.

26

3.0 Operation