2.0 Installation

14

Figure 9, DC Cable to Battery Terminals

DC Cable Connections

When connecting the DC cable to the battery or to the inverter’s DC

terminals, the hardware should be installed in the correct order to

prevent high resistance connections from heating up and possibly

causing the connections to melt. Follow Figures 9 and 10 to stack

the hardware correctly. Tighten the terminal connections from 10 to

12 foot-pounds.

CAUTION: Do not put anything between the DC cable ring

lug and the battery terminal post or inverter’s DC terminal.

If antioxidant grease or spray is used, apply it after all the

connections have been made and are properly tightened.

CAUTION: Overtightening or misthreading nuts on the DC

terminals will cause the bolts to strip and snap/break-off.

CAUTION: The inverter is NOT reverse polarity protected

(negative and positive connected backwards). You must

verify the correct voltage polarity BEFORE connecting the

DC wires or damage may occur.

Crimped and sealed copper ring terminal lugs with a 5/16” hole should

be used to connect the DC wires to the inverter’s DC terminals.

Figure 10, DC Cable to Inverter’s DC Terminals

B A T T ER Y

D C cable

w ith ring lug

bolt

flat w asher

nut

lock w asher

battery

post

battery term inal

T em perature sensor

Verify that the

DC cable lugs are flush

with the battery terminals.

T orque the battery terminals

from 10 to 12 foot-pounds.

D C cable

w ith ring lug

D C

term inal cover

(snaps on)

Inverter’s

D C term inal

5 /16

” (Kep

nut w ith star-w asher) or

F lange nut