AC Input Wiring
Your inverter has an AC transfer feature that passes the AC input

power to the inverter’s output. Connection to the AC input is made

by hardwiring from a distribution panel as described below:
1. Run an appropriately sized 2-conductor plus ground cable (from the

AC distribution panel) through a strain relief on the AC IN opening.

Refer to Table 4 for minimum wire size and overcurrent protection

required for the AC input wiring.
2. Remove about two inches of the insulating jacket from the AC

cable, and then separate the three wires and strip about 3/4” of

insulation from each wire.
3. Using approved AC wire connectors, connect the incoming Hot

In, Neutral In, and Ground wires to the MM-AE Series’ AC wires

colored black (HOT IN), white (NEU IN), and green (AC GROUND)

respectively.
4. After making the AC input connections, secure the AC input cable

by tightening the strain relief.
The AC input wiring in the inverter is complete. Review all AC wiring

to ensure all connections are correct and secure.

19

Table 4, Minimum Wire Size to Circuit-breaker Size

2.0 Installation

Overcurrent protection must be provided by fuses or circuit-breakers,

and must

be properly sized and rated for the wire they are protecting

and the appliances being powered.

An external disconnect device is required for both the AC input and

AC output wiring. Most inverter’s that are “hardwired” use a service/

distribution panel wired to the inverter’s input (main panel), and a

dedicated panel between the inverter’s output wiring and the AC loads

(sub-panel). These systems use the circuit breakers provided in the

panels as the overcurrent protection and the AC disconnect. If fuses

are used, then separate AC disconnect switches will be needed.
Based on information from the NEC, Table 4 provides the minimum

AC wire size and the suggested breaker size based on the inverter

model. H

owever, larger wire size may be required because of volt-

age drop. The

AC wire sizes provided in this table assume using only

copper wire and a temperature rating of 75° C or higher. A minimum

of #14 AWG is required for all AC wiring.

Inverter

Model

AC Input

AC Output

Input

Breaker

Minimum

Wire Size

Suggested

Breaker

Size

Output

Breaker

Minimum

Wire Size

Suggested

Breaker

Size

MM612AE

7 amps

#14 AWG

10 amps

8 amps

#14 AWG

10 amps

MM1512AE 20 amps #12 AWG

20 amps

12 amps #14 AWG

15 amps

MM1524AE 20 amps #12 AWG

20 amps

12 amps #14 AWG

15 amps