2.0 Installation

AC Output Wiring

CAUTION: The inverter’s AC output must never be con-

nected to an AC power source. This will cause severe

damage to the inverter and is not covered under war-

ranty.

When hardwiring the output of the inverter, a cable must be routed

from the inverter’s output to an AC distribution panel (sub-panel)

that provides overcurrent protection to the loads powered by the in-

verter. Connect the AC output to this distribution panel as described

below:

1. Remove the 1/2” knockout on the AC Output Connection

(see Figure 4, Item 15) – use a utility knife to cut thru the round

slot.
2. Discard this knockout and install a 1/2” strain relief in the AC OUT

opening. You may need to fi le the opening edge for proper fi t.
3. Run a 2-conductor plus ground cable through the strain relief in

the AC OUT opening. Refer to Table 4 for the minimum wire size and

the overcurrent protection required for the AC output wiring.

AC IN

AC O UT

Strain

reliefs

A C

Ground

In/Out

(g re e n)

N eutral

In

(w h ite)

H ot

Out

(re d)

N eutral Out

(w h ite w/b la ck

strip e )

H ot

In

(b la ck)

Figure 11, AC Wiring Connections