beautypg.com

Magnum Energy MM-AE Series User Manual

Page 14

background image

©

2010 Magnum Energy, Inc.

2.0 Installation

8

Locating and Mounting the Inverter

WARNINGS:
• Do not mount the inverter near any fl ammable or

combustible fl uid or components.

• Provide adequate clearance/ventilation to the inverter.
• Mount only on a non-combustible surface.
• Maximum ambient temperature around the inverter must

not exceed 77° F (25° C) to meet power specifi cations.

The inverter should only be installed in a location that meets the

following requirements:
Clean and Dry - The inverter should not be installed in an area that

allows

dust, fumes, insects, or rodents to enter or block the inverter’s

ventilation openings. The area also must be free from any risk of

condensation, water,

or any other liquid that can enter or fall on the

inverter. The inverter uses stainless steel fasteners, plated copper

busbars, and a power-coated aluminum base. Also, the internal circuit

boards are conformal coated. The above measures are undertaken

to help fi ght the harmful effects of corrosive environments. However,

the life of the inverter is uncertain if used in any of these types of

environments, and inverter failure under these conditions is not covered

under warranty.
Cool - The inverter should be

protected from direct exposure to the

sun or any equipment that produces extreme heat.

The ambient air

temperature should be between 32° F (0° C) and 104° F (40° C);

keep in mind that the inverter’s output specifi cations are rated at 77°

F (25° C), so the cooler the better within this range.

Ventilated - In order for the inverter to provide full output power

and avoid over-temperature fault conditions do not cover or block

the inverter’s ventilation openings, or install this inverter in an area

with limited airfl ow. Allow as much clearance around the inverter’s

intake and exhaust ventilation openings as possible, see Items 12

and 13 in Figure 3. At the minimum, allow an airspace clearance of

6” (15 cm) at the front and back, and 3” (7.5 cm) everywhere else

to provide adequate ventilation.

If installed in an enclosure, a fresh air intake opening must be pro-

vided directly to the front side (intake vent) and an exhaust open-

ing on the back side (exhaust vent) of the inverter. This will allow

cool air from the outside to fl ow into the inverter, and heated air to

exit away from the inverter and the enclosure. When mounted in an

enclosed compartment, airfl ow must be at least 59 cfm in order to

maintain no more than a 68° F (20° C) rise in compartment tem-

perature. Minimum clearances can be reduced if airfl ow is increased,

but in no case should clearance around the inverter be less than 2”

(5 cm) on all sides.

This manual is related to the following products: