Troubleshooting Guide

3/21/96

Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

Table 3. Troubleshooting Guide – Continued

274

(continued)

275

276

277

278

290

291

292

293

294

295

296

298

300

301

302

303

304

305

306

307

308

Not a Parameter File

Flash RAM Program 00 Error

Flash RAM Program FF Error

Flash RAM Verify Error

Board Status Bus Error

Board Control Bus Error

D/A 1 Bus Error

D/A 2 Bus Error

A/D Bus Error

Clock Bus Error

Tachometer Bus Error

Expansion 2 Bus Error

Board Status Address Error

Board Control Address Error

D/A 1 Address Error

D/A 2 Address Error

A/D Address Error

Clock Address Error

Tachometer Address Error

Expansion 1 Address Error

Expansion 2 Address Error

If drive has failed to stop motor, replace
main drive PCB board. See “Replacing
Drive Control PCB”/Maintenance Section.

YMODEM transfer is stopped. The .PAR
file is corrupt or not in the correct format
to be a .PAR file.

Re-down load with backup .PAR file.

YMODEM transfer is stopped. The .PRG
file does not agree with the PROMs
installed in the drive.

Replace Main drive PCB or flash ROM
chips. See “Replacing Drive Control
PCB”/Maintenance Section.

CPU halted.
Communications Failure
.

Call MagneTek for field service
assistance.