Electrical hook-up addendum, Microtrac digital system drives – Yaskawa DSD 406 User Manual
Page 111

MICROTRAC
DIGITAL
SYSTEM
DRIVES
Electrical Hook-up Addendum
ARM(–): Using 600V vinyl-sheathed wire per the following table.
Recommended Wire Gauge (Copper Only)
Torque
Drive Hp
60°C
75°C
90°C
(in-lbs)
2
14
14
35
3
14
14
35
5
14
14
35
7
6
8
45 - 40 *
10
6
8
45 - 40 *
15
4
4
45
20
4
4
45
25
3
50
30
3
50
40
1/0
50
50
1/0
50
60
3/0
50
75
250 MCM
325
100
250 MCM
325
125
350 MCM
325
150
500 MCM
375
200
700 MCM
375
* Torque per wire gauge.
ARM(+): Using 600V vinyl-sheathed wire per the following table.
Recommended Wire Gauge (Copper Only)
Torque
Drive Hp
60°C
75°C
90°C
(in-lbs)
2
14
14
35
3
14
14
35
5
14
14
35
7
6
8
45 - 40 *
10
6
8
45 - 40 *
15
4
4
45
20
4
4
45
25
3
50
30
3
50
40
1/0
180
50
1/0
180
60
3/0
250
75
250 MCM
325
100
250 MCM
325
125
350 MCM
325
150
500 MCM
375
200
700 MCM
375
* Torque per wire gauge.
PAGE 2
TM 6107 Addendum 1
© Copyright 1995 MagneTek, Inc.