VS-616G5 Programming Manual

Section F: Option Parameters

F3 DI-08/DI-16H & F4 AO-08/AO-12 Option

F3

DI-08/DI-16H Set-up

Selects the setting mode of the frequency reference input from the DI-08 and DI-16H options.

F4

AO-08/AO-12 Set-up

Selects the analog output monitors for channel 1 of the AO-08 and AO-12 options.

F3-01 Digital Input Option

DI Input

A

A

A

A

Setting

Frequency Reference Setting Mode

0

BCD 1% unit (factory default)

1

BCD 0.1% unit

2

BCD 0.01% unit

3

BCD 1Hz unit

4

BCD 0.1Hz unit

5

BCD 0.01Hz unit

6

Binary
DI-08:

255/100%

DI-16H, 12-bit selection:

4096/100%

DI-16H, 16-bit selection:

30000/100%

7

Binary, set value is displayed in decimal notation.

F4-01 Analog Output Channel 1 Selection

AO CH1 Select

A

A

A

A

Analog Output Channel 1 Selection

F4-01 Setting

Function

Description

1

Frequency reference

Monitors the frequency reference value. 10V= Max frequency

(0-+/-10V possible)

2

Output frequency (factory default)

Monitors the output frequency. 10V= Max frequency

(0-+/-10V possible)

3

Inverter output current

Monitors the output current. 10V=Rated current (0 to +10V output)

5

Motor speed

Monitors the motor speed. 10V= Max frequency (0 to +/- 10 V possible)

6

Output voltage

Monitors the inverters internal output voltage reference value.

10V=200,400 or 575 VAC

7

DC bus voltage

Monitors the DC voltage of the inverters internal main circuit.

10V=400 or 800 VDC (0 to +10V output)

8

Output power

Monitors the output power, this is an internally detected value. 10V=Max motor

capacity. (0 to +/-10 V possible)

9

Torque reference (internal)

Monitors the internal torque reference value when vector control is used.

10 V=Rated torque. (0 to +/-10V possible)

10-14

Not Used

--

15

Terminal 13 input voltage level

Monitors the input voltage of the frequency reference (voltage). An input of 10 V

corresponds to 100%. 10 V=100% (10 V) 0 to +/-10 V possible.

16

Terminal 14 input voltage or current level

Monitors the input current of the frequency reference. (current) An input of 20 mA

corresponds to 100%. 20 mA=100% (20 mA) 0 to + 10 V output.

17

Terminal 16 input voltage level

Monitors the input voltage of the multi-function analog input. An input of 10 V cor-

responds to 100%. 10 V= 100% (10 V). (0 to +/-10 V possible)