Analog output channel 1 selection – Yaskawa VS-616G5 Series Revision F Programming Manual User Manual
Page 68
V/f
V/f w/PG Open Loop
Vector
Flux
Vector
68
VS-616G5 Programming Manual
Section F: Option Parameters
F3 DI-08/DI-16H & F4 AO-08/AO-12 Option
F3
DI-08/DI-16H Set-up
Selects the setting mode of the frequency reference input from the DI-08 and DI-16H options.
F4
AO-08/AO-12 Set-up
Selects the analog output monitors for channel 1 of the AO-08 and AO-12 options.
F3-01 Digital Input Option
DI Input
A
A
A
A
Setting
Frequency Reference Setting Mode
0
BCD 1% unit (factory default)
1
BCD 0.1% unit
2
BCD 0.01% unit
3
BCD 1Hz unit
4
BCD 0.1Hz unit
5
BCD 0.01Hz unit
6
Binary
DI-08:
255/100%
DI-16H, 12-bit selection:
4096/100%
DI-16H, 16-bit selection:
30000/100%
7
Binary, set value is displayed in decimal notation.
F4-01 Analog Output Channel 1 Selection
AO CH1 Select
A
A
A
A
Analog Output Channel 1 Selection
F4-01 Setting
Function
Description
1
Frequency reference
Monitors the frequency reference value. 10V= Max frequency
(0-+/-10V possible)
2
Output frequency (factory default)
Monitors the output frequency. 10V= Max frequency
(0-+/-10V possible)
3
Inverter output current
Monitors the output current. 10V=Rated current (0 to +10V output)
5
Motor speed
Monitors the motor speed. 10V= Max frequency (0 to +/- 10 V possible)
6
Output voltage
Monitors the inverters internal output voltage reference value.
10V=200,400 or 575 VAC
7
DC bus voltage
Monitors the DC voltage of the inverters internal main circuit.
10V=400 or 800 VDC (0 to +10V output)
8
Output power
Monitors the output power, this is an internally detected value. 10V=Max motor
capacity. (0 to +/-10 V possible)
9
Torque reference (internal)
Monitors the internal torque reference value when vector control is used.
10 V=Rated torque. (0 to +/-10V possible)
10-14
Not Used
--
15
Terminal 13 input voltage level
Monitors the input voltage of the frequency reference (voltage). An input of 10 V
corresponds to 100%. 10 V=100% (10 V) 0 to +/-10 V possible.
16
Terminal 14 input voltage or current level
Monitors the input current of the frequency reference. (current) An input of 20 mA
corresponds to 100%. 20 mA=100% (20 mA) 0 to + 10 V output.
17
Terminal 16 input voltage level
Monitors the input voltage of the multi-function analog input. An input of 10 V cor-
responds to 100%. 10 V= 100% (10 V). (0 to +/-10 V possible)