Monitor display (un-xx) – Yaskawa VS-616G5 Series Revision F Programming Manual User Manual

Page 157

background image

VS-616G5 Programming Manual

157

2. Monitor Display (Un-XX)

Fu

nc

tio

n

Parameter

No.

Name

(Digital Operator Display)

Min.

Unit

Description

Analog

Monitor

Output Level

Parameter Access Level

V/f

V/f w/

PG

Vector

w/o

PG

Vector

w/ PG

M

on

ito

r

U1-01

Frequency Reference
(Frequency Ref)

0.01Hz The unit differs depending on O1-03 setting.

10V/Max.

output

frequency

Q

Q

Q

Q

U1-02

Output Frequency
(Output Freq)

0.01Hz The unit differs depending on O1-03 setting.

10V/Max.

output

frequency

Q

Q

Q

Q

U1-03

Output Current
(Output Current)

0.1A

Minimum unit is 0.01 A for 7.5 kW or less.

10V/Inverter

rated

current

Q

Q

Q

Q

U1-04

Control Method*
(Control Method)

0: V/f control
1: V/f control with PG
2: Vector control without PG
3: Vector control with PG

Q

Q

Q

Q

U1-05

Motor Speed
(Motor Speed)

0.01Hz The unit differs depending on O1-03 setting.

10V/Max.

output fre-

quency

x

Q

Q

Q

U1-06

Output Voltage
(Output Voltage)

0.1V

10V/200V or

400V

?575

Q

Q

Q

Q

U1-07

DC Bus Voltage V
(DC Bus Voltage)

1V

10V/400V or

800V

Q

Q

Q

Q

M

on

ito

r

U1-08

Output Power
(Output kWatts)

0.1kW

10V/Inverter

capacity

(kW)

Q

Q

Q

Q

U1-09

Torque Reference
(Torque Reference)

0.1%

10V/Motor

rated torque

x

x

Q

Q

U1-10

Input Terminal Status*
(Input Term Sts)

Q

Q

Q

Q

U1-11

Output Terminal Status*
(Output Term Sts)

Q

Q

Q

Q

0

1: T1 “Closed”

1: T2 “Closed”

1: T3 “Closed”

1: T4 “Closed”

1: T5 “Closed”

1: T6 “Closed”

1: T7 “Closed”

1: T8 “Closed”

0 0 0 0 0 0 0

1: T9~ 10 “Closed”

1: T25 “Closed”

1: T26 “Closed”

0: Not used

0: Not used

0: Not used

0: Not used

1: Fault

0 0 0 0 0 0 0 0

Appendix

VS-616G5 Parameter List U Monitor

* Cannot be changed by U1-04