VS-616G5 Programming Manual
Section H: Control Circuit Terminals
H5 Serial Communication Set-up
Selects the stopping method after a transmission error is detected.
H5-05 enables or disables the MODBUS time out detection function. After initial communication
begins, if communication is interrupted for longer than 2 seconds, then a communication fault will
occur.
During a communication fault, the following fault code will be displayed: “CE Memobus Com Err”.
L
Protection Parameters
L1
Motor Overload
The VS-616G5 protects against motor overload with a UL-recognized, built-in electronic thermal
overload function.
Selects whether motor overload protection is provided.
The electronic thermal overload function estimates motor temperature, based on inverter output cur-
rent and time, to protect the motor from overheating. When the electronic thermal overload relay is
activated, an “OL1” error occurs, shutting OFF the inverter output and preventing excessive overheat-
ing in the motor. As long as the inverter is powered up, it continues to calculate the motor temperature.
When operating with one inverter connected to one motor, an external thermal relay is not needed.
H5-04 Stopping Method After Communication Error
Serial Fault Sel
A
A
A
A
Setting
Description
0
Ramp to stop according to the time set in C1-02.
1
Fast-stop according to the time set in C1-09.
2
Coast to stop
3
Alarm only, continuous operation (factory default)
H5-05 MODBUS Time Out Detection
Serial Fault Dtct
A
A
A
A
Setting
Description
0
Disabled - Time out detection is disabled.
1
Enabled - Time out detection is enabled.
L1-01
Motor Protection Fault Selection (OL1)
MOL Fault Select
B
B
B
B
Setting
Description
0
Motor overload detection is disabled.
1
Motor overload detection is enabled,
motor coasts to stop (factory default).