V/f

V/f w/PG Open Loop

Vector

Flux

Vector

A2

User’s Parameters
The user can select up to 32 parameters for quick-access programming. By setting the user access level
(A1-01) to “User Program”, only the parameters selected in function A2 can be accessed by the user.

Parameter A1-01 must be set to 4 (advanced access level) to input parameter numbers into A2-01
through A2-32, and then A1-01 must be set to 1 (User Level) for only the user selected parameters to
be viewed.

Main Menu: Programming

B

Application Parameters

B1

Sequence

Frequency reference and run command can be set independently as shown below:

*

Setting parameter B1-01 or B1-02 to 4 allows reference and/or run source from CP-717 when

either CP-916 or CP-216 option cards are installed.

By depressing the LOCAL/REMOTE key on the digital operator, the operation mode can be
selected as shown below:

Local:

Operation according to frequency reference and run command from digital operator.

Remote: Operation according to frequency reference and run command set by B1-01 and B1-

02.

The digital operator is reset to remote operation when power is cycled.

B1-01 Frequency Reference Selection

Reference Source

Q

Q

Q

Q

B1-02 Operation Method Selection

Run Source

Q

Q

Q

Q

Setting

Description

0

Command from digital operator

1

Command from control circuit terminal (factory default)

2

Command from serial communication

3

Command from option card

4

EWS (Reference from CP-717)*

<1110>

This setting will be used with the CP-717 to run and change
the reference through DP-RAM.

Section B: Application Parameters

A2 User Parameters and B1 Sequence