Yaskawa VS-616G5 Series Revision F Programming Manual User Manual
Page 45
VS-616G5 Programming Manual
45
V/f
V/f w/PG Open Loop
Vector
Flux
Vector
D
Reference Parameters
D1
Preset References
Setting Range:
0.0 to 400.0Hz
Factory Default:
0.0Hz
Up to 9 preset speed references (including jog) can be set through multi-function contact input func-
tion selections. When using the multi-step speed references, set the reference selection (B1-01) to “0”,
and set terminal 16 selection (H3-05) to “1F”. See the following table for programming preset speed
references.
D1-01 Preset Frequency Reference 1
Reference 1
Q
Q
Q
Q
D1-02 Preset Frequency Reference 2
Reference 2
Q
Q
Q
Q
D1-03 Preset Frequency Reference 3
Reference 3
Q
Q
Q
Q
D1-04 Preset Frequency Reference 4
Reference 4
Q
Q
Q
Q
D1-05 Preset Frequency Reference 5
Reference 5
B
B
B
B
D1-06 Preset Frequency Reference 6
Reference 6
B
B
B
B
D1-07 Preset Frequency Reference 7
Reference 7
B
B
B
B
D1-08 Preset Frequency Reference 8
Reference 8
B
B
B
B
Terminal 5
H1-03
= “3”
Terminal 6
H1-04
= “4”
Terminal 7
H1-05
= “5”
Terminal 8
H1-06
= “6”
Speed Reference
Open
Open
Open
Open
Speed Reference 1 - Set Reference Source
(B1-01)
to “0”.
Closed
Open
Open
Open
Speed Reference 2 - Set Terminal 16 Selection
(H3-05)
to “1F”.
Open
Closed
Open
Open
Speed Reference 3
Closed
Closed
Open
Open
Speed Reference 4
Open
Open
Closed
Open
Speed Reference 5
Closed
Open
Closed
Open
Speed Reference 6
Open
Closed
Closed
Open
Speed Reference 7
Closed
Closed
Closed
Open
Speed Reference 8
Closed
Closed
Closed
Closed
Jog Speed Reference
Section D: Reference Parameters
D1 Preset References