Setting Range:

0.0 to 400.0Hz

Factory Default:

0.0Hz

The jog frequency reference can be set in this parameter. Depress the JOG key on the digital
operator, or close terminal 7, to use this function. The jog command always has priority over
other reference commands. When using the multi-step speed references, change the jog com-
mand from terminal 7 to terminal 8 (H1-06 = “6”).

Note:

Setting units for D1-01 to D1-09 are dependent upon the setting of digital operator display
mode (O1-03). Possible setting units include Hz, percentage, RPM or engineering units. See
section O1, Monitor Selection, on page 120 for more details.

D1-09 Jog Frequency Reference

JOG Reference

Q

Q

Q

Q

Multi-step Speed Ref. 1

Frequency

Reference

FWD (REV) Run/Stop

(Terminal 5)

Multi-step Speed Ref. 2

(Terminal 6)

D1-04

40.0Hz

D1-01

10.0Hz

D1-02

20.0Hz

D1-03

30.0Hz

ON

ON

ON

ON

Figure 24 Multi-step Speed Operation - Timing Diagram

Multi-step Speed Ref. 3

(Terminal 7)

Jog Ref.

(Terminal 8)

ON

ON

ON

ON

ON

D1-05

45.0Hz

D1-06

50.0Hz

D1-07

55.0Hz

D1-08

60.0Hz

D1-09

6.0Hz

Time

Section D: Reference Parameters

D1 Preset References