VS-616G5 Programming Manual
117
Selects the stopping method when heatsink overheat is detected.
The input phase loss detection circuit monitors the DC bus current ripple and activates when the one of
the input phases are lost. The detection circuit calculates the maximum and minimum values of the DC
bus voltage in one second intervals, and compares the difference (
∆
V) between these values with an inter-
nal detection level. If
∆
V reaches or exceeds the detection level, then after 0.5 second, input phase loss is
detected; a PF fault occurs, and the motor coasts to stop.
Input phase loss detection is disabled in the following cases:
· A Stop command is input.
· Magnetic Contactor (MC) shuts OFF.
· CPU A/D converter fault (CPF5).
· During deceleration.
· Output current
≤
30% of Inverter rated current.
L8-03 Stopping Method Selection After OH Pre-Alarm
OH Pre-Alarm Sel
A
A
A
A
Setting
Description
0
Ramp to stop according to C1-02 setting.
1
Coast to stop
2
Ramp to stop according to C1-09 setting (fast-stop).
3
Operation continues, alarm only (factory default).
L8-05 Input Phase Loss Protection
Ph Loss In Sel
A
A
A
A
Setting
Description
0
Input phase loss protection is disabled (factory default).
1
Input phase loss protection is enabled.
Section L: Protection Parameters
L8 Hardware Protection